SlideShare ist ein Scribd-Unternehmen logo
1 von 58
Downloaden Sie, um offline zu lesen
Chapter V
Application of Capacitors to
Distribution System and Voltage
Regulation
POWER FACTOR IMPROVEMENT
Introduction:
• The electrical energy is almost exclusively generated, transmitted and
distributed in the form of alternating current. Therefore, the question of
power factor immediately comes into picture. M
• Most of the loads (e.g. induction motors , arc lamps) are inductive in
nature and hence have low lagging power factor. The low power factor is
highly undesirable as it causes an increase in current, resulting in an
additional losses of active power in all the elements of power system from
power station generator down to the utilization device.
• In order to ensure most favourable conditions for a supply system from
engineering and economical standpoint , it is important to have power
factor as close to unity as possible.
The cosine of angle between voltage and currentin an a.c. circuit is
known as power factor.
Power Triangle
Disadvantages of Low Power Factor
Power Factor Improvement
Power Factor Improvement Equipment
Calculations of Power Factor correction
Nomogram for calculating Multiplication factor
Problem
A single phase motor connected to 400 V, 50 Hz supply takes 31·7A at a power
factor of 0·7 lagging. Calculate the capacitance required in parallel with the motor
to raise the power factor to 0·9 lagging.
A 3-phase, 5 kW induction motor has a p.f. of 0·75 lagging. A bank of capacitors
is connected in delta across the supply terminals and p.f. raised to 0·9 lagging.
Determine the kVAR rating of the capacitors connected in each phase.
Problem:
The load on an installation is 800 kW, 0·8 lagging p.f. which works for 3000
hours per annum. The tariff is Rs 100 per kVA plus 20 paise per kWh. If the power
factor is improved to 0·9 lagging by means of loss-free capacitors costing Rs 60 per
kVAR, calculate the annual saving effected. Allow 10% per annum for interest and
depreciation on capacitors.
The operating power from distribution system is composed of both active and
reactive elements. The typical daily load curves (reactive and active power) for
a 66kV feeder is given in Fig.
Real and Reactive Power Demand
The reactive power is consumed by overhead lines, transformers
and loads. Its proper generation and control is important for
maintaining the network voltage under normal and abnormal
power system operation and to reduce system losses.
The system voltage collapse due to lack of global control of
reactive power flow during crucial grid has collapsed many times
during the past few years due to lack of reactive power in the
region.
Cost per kVAr of reactive power generation varies between 2 per
cent and 4 per cent of per kW installed regulating controls. The
system should be planned for carrying out suitable proportion of
reactive energy.
Reactive Power Consumption by lines:
•The distribution lines consume reactive power (I2X) depending upon
the series reactance (X) and load current (I). The series reactance of
line is proportional to the conductor self – inductance, which decreases
as the spacing between conductors decreases.
•The minimum spacing is kept such as to prevent flash- over in foul
weather conditions. According to a study of rural area , the average
reactive power consumed by primary HT (11kV) and LT lines for each
transformer at full-load is almost 1 per cent of transformer rating. The
underground cable (11 kV and above) generate reactive power (Ic
2Xc)
depending upon the capacitive reactance (Xc) and charging current (Ic)
at rated voltage.
Reactive Power Consumption by lines:
•Increasing the line voltage at transformer and motors above the rated
voltage will increase the consumption of reactive energy, the extent of
which depends upon their designs. Generally, increase of 10% of the
rated voltage will result in about 20% reduction of power factor.
Reactive Power Consumption by Distribution
Transformers
The reactive power consumption takes place in the series leakage and the
shunt magnetizing reactances. The second component is voltage
dependent, while the first component is proportional to the square of the
transformer current. A completely unloaded transformer would be very
inductive and has a very low power factor. The reactive power used by a
transformer (up to 100 kVA capacity) at full load and at rated voltage is
approximately 7-9 % of the rated power of the transformer. When
unloaded, the amount of reactive power remains between 3 and 4 % of
the rated power.
Reactive Power Consumption by Loads
Loads have varying reactive power requirement. The low power
factor can be a result of the equipment as in case of welders, or it
can result from the operating conditions under which equipment is
used as lightly loaded transformers and lightly loaded induction
motors.
Reactive Power Compensation and Voltage
control
Mainly capacitors are used to develop reactive power near the point of
consumption. For capacitor compensation at load, the user reaps the same
advantage as the power utility for higher power factor on small scale.
Also, if each load is compensated, the power factor remains
relatively constant since in plants, loads are switched on and off and the
dangers of over – compensation do not exist.
Suitable capacitor banks at grid or main sub- station are
desirable to feed reactive requirement of lines, transformers and domestic
consumers, etc., who have no capacitors at terminals.
Over Compensation
At the point of capacitors over-compensation, the voltage
rises and capacitive kVAr will export, i.e. it will flow to
reverse side of the load. Under certain conditions,
dangerously high transient voltage may prevail on the
power lines.
Also, torque surges of over 20 times the motor
rating can be transmitted to the motor shaft under rapid
restart conditions. Over-compensation at consumer
premises is not generally desirable.
Typical capacitor connection at Transformer
The minimum capacitor size can be connected permanently
on secondary terminals, irrespective of load. This is the value
of capacitance required to compensate the no-load
magnetizing kV A of the transformer.
Transformer KVA * % Impedance
Minimum Capacitor in KVAr = _______________________________
200
Typical scheme for automatic control of LT capacitors at
distribution transformers
The minimum number of units required to limit the voltage increase to 10% can
be calculated from the following equation for the grounded star bank.
Where N = Minimum number of parallel units in one series section
S = Number of series sections in each phase.
System Harmonics
With the increasing use of rectifiers, thyristor control
shunt capacitors, etc. the harmonic generation can create
problems with sensitive electronic equipment which can lead
to errors in the protective gear, metering and control systems
and also overload the capacitor banks besides causing
resonance.
Reactors are sometimes needed to reduce the total current
drawn by the capacitor banks if unduly large harmonics are
present in the system voltage.
The causes of harmonics in the power system
• Over-excited
transformers
• Mercury rectifiers and
thyristors
• Arc furnaces
• Slot harmonics of rotary
machine
• Corona loss
• Large motors running at
low slip, fluorescent
lighting , T.V. and radio
equipment
• System switching and
load chocking
Inrush Currents
When the capacitor banks are connected parallel to the
supply, the initial charging current is said be inrush current. The
inrush current can be reduced by connecting the series damping
reacors.
In the case of single capacitor bank, the damping reactor
is not normally required from the consideration of inrush currents
at the time of switching.
The system reactance including the transformer to
which the capacitor bank is installed is adequate enough to bring
down the value of inrush currents with in safe limit of the capacitor
or switchgear.
Even otherwise the duration of inrush current is so small
, of the order of few cycles only, that their effect can be ignored.
When a number of capacitor banks are used in parallel, it may
become necessary to use series reactors for limiting the inrush
currents.
Assuming the severest condition of switching , the value of damping reactors in
henries is given by
The maximum peak inrush current can be approximately given by the
formula
Where,
Ic1 = capacitor’s rated current (fundamental wave) rms
Xc1 = capacitor reactance (fundamental wave)
Xl1 = total inductive reactance of the system including capacitor bank
(fundamental wave)
In case of parallel banks, which are already energized, the
inrush current is predominantly governed by the
momentary discharge from the energized banks and since
the impedance between the energized capacitor bank and
the capacitor bank to be energized may be small, it may
result in high peak inrush current. The maximum peak
current is given by the expression
C= equivalent capacitance of the circuit in H
L= equivalent series inductance between the
energized banks and bank to be energized in H
En1 = line to neutral voltage
Example
Two 11 kV capacitors banks, each of 2.5 MVAr, are installed in
parallel at a 132/11 kV sub-station. Calculate the value of the series
damping reactor with each capacitor bank
Solution
Load Utilized Voltage
10 kW 230 V
10-50 kW 415/230 V
50 kW-5 MW 11 kV
5 MW-30 MW 33-66 kV
30 MW-50MW 132 kV
Above 50 MW 220 kV
Different Consumers Voltage Standards
Voltage Regulation
Methods of Voltage Control
Importance Of Voltage Control
When the load on the supply system changes, the
voltage at the consumers' terminals also changes.
The variations of voltage at the consumer's
terminals are undesirable and must be kept within
prescribed limits for the following reasons :
(i) In case of lighting load, the lamp characteristics are very
sensitive to changes of voltage. For instance, if the supply voltagip
to an incandescent lamp decreases by 6% of rated value, then
illuminating power may decrease by 20%. On the other hand, if
the supply voltage is 6% above the rated value, the life of the
lamp may be reduced by 50% due to the rapid deterioration of
the filament.
(ii) In case of power load consisting of induction motors,
the voltage variations may cause erratic operation. If the supply
voltage is above the normal, the motor may operate with a
saturated magnetic circuit, with consequent large magnetising
current, heating and low power factor. On the other hand, if the
voltage is too low, it will reduce the starting torque of the motor
considerably.
(iii) Too wide variations of voltage cause excessive heating of
distribution transformers. This may reduce their ratings to a
considerable extent.
It is clear from the above discussion that voltage variations in a
power system must be kept to minimum level in order to deliver
good service to the consumers. With the trend towards larger
and larger interconnected system, it has become necessary to
employ appropriate methods of voltage control.
Methods Of Voltage Control
There are several methods of voltage control. In each method,
the system voltage is changed in accordance with the load to
obtain a fairly constant voltage at the consumer's end of the
system. The following are the methods of voltage control in an
a.c. power system:
(i) By excitation control
(ii) By using tap changing transformers
(iii) Auto-transformer tap changing
(iv) Booster Transformers
(v) Induction Regulators
(vi) By Synchronous Condensors
Method (i) is used at the generating station only whereas methods
(ii) to (v) can be used for transmission as well as primary
distribution systems. However, method
Tap-Changing Transformers
Off load tap-changing transformer
Figure shows the arrangement where a number of tappings
have been provided on the secondary. As the position of the
tap is varied, the effective number of secondary turns is varied
and hence the output voltage of the secondary can he
changed.
Thus referring to Fig. when the movable arm makes contact
with stud 1, the secondary voltage is minimum and when
with stud 5, it is maximum. During the period of light load,
the voltage across the primary is not much below the
alternator voltage and the movable arm is placed on stud 1.
When the load increases,
the voltage across the primary drops, but the secondary
voltage can be kept at the previous value by placing the
movable arm on to a higher stud. Whenever a tapping is to be
changed in this type of transformer, the load is kept off and
hence the name off load tap. changing transformer
ON load tap-changing transformer

Weitere ähnliche Inhalte

Was ist angesagt?

POWER SYSTEM PROTECTION
POWER SYSTEM PROTECTION POWER SYSTEM PROTECTION
POWER SYSTEM PROTECTION moiz89
 
FACTS DEVICES AND POWER SYSTEM STABILITY ppt
FACTS DEVICES AND POWER SYSTEM STABILITY pptFACTS DEVICES AND POWER SYSTEM STABILITY ppt
FACTS DEVICES AND POWER SYSTEM STABILITY pptMamta Bagoria
 
3. INTRODUCTION TO PROTECTIVE RELAYING.pptx
3. INTRODUCTION TO PROTECTIVE RELAYING.pptx3. INTRODUCTION TO PROTECTIVE RELAYING.pptx
3. INTRODUCTION TO PROTECTIVE RELAYING.pptxMuhd Hafizi Idris
 
Power Quality and Monitoring
Power Quality and MonitoringPower Quality and Monitoring
Power Quality and Monitoringash08031996
 
Various Bus-Bar Arrangements.
Various Bus-Bar Arrangements.Various Bus-Bar Arrangements.
Various Bus-Bar Arrangements.SaiSampath16
 
surge diverters
surge diverterssurge diverters
surge divertersnehakardam
 
Methods of Voltage Control
Methods of Voltage ControlMethods of Voltage Control
Methods of Voltage ControlYashvi Mehta
 
Power System Control And Line Compensation
Power System Control And Line CompensationPower System Control And Line Compensation
Power System Control And Line CompensationAnakin Akshat Assal
 
Power system protection topic 1
Power system protection topic 1Power system protection topic 1
Power system protection topic 1Siswoyo Edo
 
Load Frequency Control of Two Area System
Load Frequency Control of Two Area SystemLoad Frequency Control of Two Area System
Load Frequency Control of Two Area SystemManash Deka
 
importance of reactive power in power system
importance of reactive power in power systemimportance of reactive power in power system
importance of reactive power in power systemsneh pratap singh
 
Protection of transmission lines (distance)
Protection of transmission lines (distance)Protection of transmission lines (distance)
Protection of transmission lines (distance)Rohini Haridas
 
Gcsc gto thyristor controlled series capacitor
Gcsc   gto thyristor controlled series capacitorGcsc   gto thyristor controlled series capacitor
Gcsc gto thyristor controlled series capacitorLEOPAUL23
 

Was ist angesagt? (20)

POWER SYSTEM PROTECTION
POWER SYSTEM PROTECTION POWER SYSTEM PROTECTION
POWER SYSTEM PROTECTION
 
Facts controller
Facts controllerFacts controller
Facts controller
 
Ac voltage
Ac voltageAc voltage
Ac voltage
 
FACTS DEVICES AND POWER SYSTEM STABILITY ppt
FACTS DEVICES AND POWER SYSTEM STABILITY pptFACTS DEVICES AND POWER SYSTEM STABILITY ppt
FACTS DEVICES AND POWER SYSTEM STABILITY ppt
 
3. INTRODUCTION TO PROTECTIVE RELAYING.pptx
3. INTRODUCTION TO PROTECTIVE RELAYING.pptx3. INTRODUCTION TO PROTECTIVE RELAYING.pptx
3. INTRODUCTION TO PROTECTIVE RELAYING.pptx
 
Power Quality and Monitoring
Power Quality and MonitoringPower Quality and Monitoring
Power Quality and Monitoring
 
Various Bus-Bar Arrangements.
Various Bus-Bar Arrangements.Various Bus-Bar Arrangements.
Various Bus-Bar Arrangements.
 
surge diverters
surge diverterssurge diverters
surge diverters
 
Methods of Voltage Control
Methods of Voltage ControlMethods of Voltage Control
Methods of Voltage Control
 
Upfc & fact
Upfc & factUpfc & fact
Upfc & fact
 
Facts lectures-2014
Facts lectures-2014Facts lectures-2014
Facts lectures-2014
 
Power System Control And Line Compensation
Power System Control And Line CompensationPower System Control And Line Compensation
Power System Control And Line Compensation
 
Protection and Switchgear
Protection and SwitchgearProtection and Switchgear
Protection and Switchgear
 
Power system protection topic 1
Power system protection topic 1Power system protection topic 1
Power system protection topic 1
 
Load Frequency Control of Two Area System
Load Frequency Control of Two Area SystemLoad Frequency Control of Two Area System
Load Frequency Control of Two Area System
 
importance of reactive power in power system
importance of reactive power in power systemimportance of reactive power in power system
importance of reactive power in power system
 
Protection of transmission lines (distance)
Protection of transmission lines (distance)Protection of transmission lines (distance)
Protection of transmission lines (distance)
 
Statcom
StatcomStatcom
Statcom
 
Static relay
Static relayStatic relay
Static relay
 
Gcsc gto thyristor controlled series capacitor
Gcsc   gto thyristor controlled series capacitorGcsc   gto thyristor controlled series capacitor
Gcsc gto thyristor controlled series capacitor
 

Andere mochten auch

Distribution System Voltage Drop and Power Loss Calculation
Distribution System Voltage Drop and Power Loss CalculationDistribution System Voltage Drop and Power Loss Calculation
Distribution System Voltage Drop and Power Loss CalculationAmeen San
 
ELECTRICAL DISTRIBUTION TECHNOLOGY
ELECTRICAL DISTRIBUTION TECHNOLOGYELECTRICAL DISTRIBUTION TECHNOLOGY
ELECTRICAL DISTRIBUTION TECHNOLOGYAmeen San
 
Automation of capacitor banks based on MVAR Requirement
Automation of capacitor banks based on MVAR RequirementAutomation of capacitor banks based on MVAR Requirement
Automation of capacitor banks based on MVAR RequirementAhmed Aslam
 
Load Characteristics
Load CharacteristicsLoad Characteristics
Load CharacteristicsAmeen San
 
automatic power factor controller
automatic power factor controllerautomatic power factor controller
automatic power factor controllersingh1515
 
Distribution systems
Distribution systemsDistribution systems
Distribution systemsSURAJ PRASAD
 
Stepper motor
Stepper motor Stepper motor
Stepper motor Ameen San
 
PLC Counters
PLC CountersPLC Counters
PLC CountersAmeen San
 
PLC arithmatic functions
PLC arithmatic functionsPLC arithmatic functions
PLC arithmatic functionsAmeen San
 
PLC application
PLC applicationPLC application
PLC applicationAmeen San
 
PLC data types and addressing
PLC data types and addressingPLC data types and addressing
PLC data types and addressingAmeen San
 
Plc analog input output programming
Plc analog input output programmingPlc analog input output programming
Plc analog input output programmingEngr Alam
 
Capacitor bank and improvement of power factor
Capacitor bank and improvement of power factorCapacitor bank and improvement of power factor
Capacitor bank and improvement of power factorAhshan Kabir
 
PLC Traffic Light Control
PLC Traffic Light ControlPLC Traffic Light Control
PLC Traffic Light ControlAmeen San
 
Engineering Economy
Engineering EconomyEngineering Economy
Engineering EconomyAmeen San
 
PLC input and output devices
PLC input and output devices PLC input and output devices
PLC input and output devices Ameen San
 
Electricity distribution system in india
Electricity distribution system in indiaElectricity distribution system in india
Electricity distribution system in indiaJasgt Singh
 
Accounting & financial decisions
Accounting & financial decisionsAccounting & financial decisions
Accounting & financial decisionsAmeen San
 

Andere mochten auch (20)

capacitors
capacitorscapacitors
capacitors
 
Distribution System Voltage Drop and Power Loss Calculation
Distribution System Voltage Drop and Power Loss CalculationDistribution System Voltage Drop and Power Loss Calculation
Distribution System Voltage Drop and Power Loss Calculation
 
ELECTRICAL DISTRIBUTION TECHNOLOGY
ELECTRICAL DISTRIBUTION TECHNOLOGYELECTRICAL DISTRIBUTION TECHNOLOGY
ELECTRICAL DISTRIBUTION TECHNOLOGY
 
Automation of capacitor banks based on MVAR Requirement
Automation of capacitor banks based on MVAR RequirementAutomation of capacitor banks based on MVAR Requirement
Automation of capacitor banks based on MVAR Requirement
 
Load Characteristics
Load CharacteristicsLoad Characteristics
Load Characteristics
 
automatic power factor controller
automatic power factor controllerautomatic power factor controller
automatic power factor controller
 
Power factor improvement
Power factor improvementPower factor improvement
Power factor improvement
 
Distribution systems
Distribution systemsDistribution systems
Distribution systems
 
Stepper motor
Stepper motor Stepper motor
Stepper motor
 
PLC Counters
PLC CountersPLC Counters
PLC Counters
 
PLC arithmatic functions
PLC arithmatic functionsPLC arithmatic functions
PLC arithmatic functions
 
PLC application
PLC applicationPLC application
PLC application
 
PLC data types and addressing
PLC data types and addressingPLC data types and addressing
PLC data types and addressing
 
Plc analog input output programming
Plc analog input output programmingPlc analog input output programming
Plc analog input output programming
 
Capacitor bank and improvement of power factor
Capacitor bank and improvement of power factorCapacitor bank and improvement of power factor
Capacitor bank and improvement of power factor
 
PLC Traffic Light Control
PLC Traffic Light ControlPLC Traffic Light Control
PLC Traffic Light Control
 
Engineering Economy
Engineering EconomyEngineering Economy
Engineering Economy
 
PLC input and output devices
PLC input and output devices PLC input and output devices
PLC input and output devices
 
Electricity distribution system in india
Electricity distribution system in indiaElectricity distribution system in india
Electricity distribution system in india
 
Accounting & financial decisions
Accounting & financial decisionsAccounting & financial decisions
Accounting & financial decisions
 

Ähnlich wie Application of Capacitors to Distribution System and Voltage Regulation

Reactive power consumption in modern power system
Reactive power consumption in modern power systemReactive power consumption in modern power system
Reactive power consumption in modern power systemRahuldey1991
 
Power factor improvement
Power factor improvementPower factor improvement
Power factor improvementharshal567
 
Synchronous condensers
Synchronous condensersSynchronous condensers
Synchronous condensersujvnl
 
power-factor-correction.pptx
power-factor-correction.pptxpower-factor-correction.pptx
power-factor-correction.pptxBabySweet5
 
power factor correction soham+niraj
power factor correction soham+nirajpower factor correction soham+niraj
power factor correction soham+nirajsoham patel
 
Energy Efficiency in Electrical Systems.pptx
Energy  Efficiency in Electrical Systems.pptxEnergy  Efficiency in Electrical Systems.pptx
Energy Efficiency in Electrical Systems.pptxPoojaAnupGarg
 
IRJET- Power Saver for Industrial and Commercial Establishments by Power Fact...
IRJET- Power Saver for Industrial and Commercial Establishments by Power Fact...IRJET- Power Saver for Industrial and Commercial Establishments by Power Fact...
IRJET- Power Saver for Industrial and Commercial Establishments by Power Fact...IRJET Journal
 
Reactive Power Compensation in 132kv & 33kv Grid of Narsinghpur Area
Reactive Power Compensation in 132kv & 33kv Grid of Narsinghpur AreaReactive Power Compensation in 132kv & 33kv Grid of Narsinghpur Area
Reactive Power Compensation in 132kv & 33kv Grid of Narsinghpur Areaijceronline
 
COMPENSATION OF REACTIVE POWER
COMPENSATION OF REACTIVE POWERCOMPENSATION OF REACTIVE POWER
COMPENSATION OF REACTIVE POWERST Chowhury
 
Unit 2 Reactive Power Management
Unit 2 Reactive Power ManagementUnit 2 Reactive Power Management
Unit 2 Reactive Power ManagementSANTOSH GADEKAR
 
Power Factor Correction.ppt
Power Factor Correction.pptPower Factor Correction.ppt
Power Factor Correction.pptSalmanHameed26
 
power factor and power factor correction schneider EMERSON EDUARDO RODRIGUES
power factor and power factor correction schneider EMERSON EDUARDO RODRIGUESpower factor and power factor correction schneider EMERSON EDUARDO RODRIGUES
power factor and power factor correction schneider EMERSON EDUARDO RODRIGUESEMERSON EDUARDO RODRIGUES
 
Reactive power management and voltage control by using statcom
Reactive power management and voltage control by using statcomReactive power management and voltage control by using statcom
Reactive power management and voltage control by using statcomHussain Ali
 
Power Factor
Power FactorPower Factor
Power FactorTim Cohen
 
Power systems voltage and power control
Power systems voltage and power controlPower systems voltage and power control
Power systems voltage and power controlCaner Göksel Sonuzun
 

Ähnlich wie Application of Capacitors to Distribution System and Voltage Regulation (20)

Reactive power consumption in modern power system
Reactive power consumption in modern power systemReactive power consumption in modern power system
Reactive power consumption in modern power system
 
Power factor improvement
Power factor improvementPower factor improvement
Power factor improvement
 
Synchronous condensers
Synchronous condensersSynchronous condensers
Synchronous condensers
 
power-factor-correction.pptx
power-factor-correction.pptxpower-factor-correction.pptx
power-factor-correction.pptx
 
Reactive power compensation
Reactive power compensationReactive power compensation
Reactive power compensation
 
STATCOM
STATCOMSTATCOM
STATCOM
 
power factor correction soham+niraj
power factor correction soham+nirajpower factor correction soham+niraj
power factor correction soham+niraj
 
Power factor
Power factorPower factor
Power factor
 
Energy Efficiency in Electrical Systems.pptx
Energy  Efficiency in Electrical Systems.pptxEnergy  Efficiency in Electrical Systems.pptx
Energy Efficiency in Electrical Systems.pptx
 
8925273.ppt
8925273.ppt8925273.ppt
8925273.ppt
 
IRJET- Power Saver for Industrial and Commercial Establishments by Power Fact...
IRJET- Power Saver for Industrial and Commercial Establishments by Power Fact...IRJET- Power Saver for Industrial and Commercial Establishments by Power Fact...
IRJET- Power Saver for Industrial and Commercial Establishments by Power Fact...
 
Reactive Power Compensation in 132kv & 33kv Grid of Narsinghpur Area
Reactive Power Compensation in 132kv & 33kv Grid of Narsinghpur AreaReactive Power Compensation in 132kv & 33kv Grid of Narsinghpur Area
Reactive Power Compensation in 132kv & 33kv Grid of Narsinghpur Area
 
COMPENSATION OF REACTIVE POWER
COMPENSATION OF REACTIVE POWERCOMPENSATION OF REACTIVE POWER
COMPENSATION OF REACTIVE POWER
 
Unit 2 Reactive Power Management
Unit 2 Reactive Power ManagementUnit 2 Reactive Power Management
Unit 2 Reactive Power Management
 
Power Factor Correction.ppt
Power Factor Correction.pptPower Factor Correction.ppt
Power Factor Correction.ppt
 
power factor and power factor correction schneider EMERSON EDUARDO RODRIGUES
power factor and power factor correction schneider EMERSON EDUARDO RODRIGUESpower factor and power factor correction schneider EMERSON EDUARDO RODRIGUES
power factor and power factor correction schneider EMERSON EDUARDO RODRIGUES
 
Reactive power management and voltage control by using statcom
Reactive power management and voltage control by using statcomReactive power management and voltage control by using statcom
Reactive power management and voltage control by using statcom
 
Facts
FactsFacts
Facts
 
Power Factor
Power FactorPower Factor
Power Factor
 
Power systems voltage and power control
Power systems voltage and power controlPower systems voltage and power control
Power systems voltage and power control
 

Mehr von Ameen San

PLC Internal Relays
PLC Internal RelaysPLC Internal Relays
PLC Internal RelaysAmeen San
 
PLC Intro to programming
PLC Intro to programmingPLC Intro to programming
PLC Intro to programmingAmeen San
 
PLC Logic Circuits
PLC Logic CircuitsPLC Logic Circuits
PLC Logic CircuitsAmeen San
 
PLC Applications
PLC ApplicationsPLC Applications
PLC ApplicationsAmeen San
 
Protection Devices and the Lightning
Protection Devices and the LightningProtection Devices and the Lightning
Protection Devices and the LightningAmeen San
 
Circuit Breakers
Circuit BreakersCircuit Breakers
Circuit BreakersAmeen San
 
Ratio analysis
Ratio  analysisRatio  analysis
Ratio analysisAmeen San
 
Depreciation methods
Depreciation methodsDepreciation methods
Depreciation methodsAmeen San
 
Income statement
Income statementIncome statement
Income statementAmeen San
 
Capital budgeting
Capital budgetingCapital budgeting
Capital budgetingAmeen San
 
Time value of money
Time value of moneyTime value of money
Time value of moneyAmeen San
 
Cash flow statement
Cash flow statementCash flow statement
Cash flow statementAmeen San
 
Forms of business organizations
Forms of business organizationsForms of business organizations
Forms of business organizationsAmeen San
 
مهارات الحوار والاقناع
مهارات الحوار والاقناعمهارات الحوار والاقناع
مهارات الحوار والاقناعAmeen San
 
Matlab solving rlc circuit
Matlab solving rlc circuitMatlab solving rlc circuit
Matlab solving rlc circuitAmeen San
 

Mehr von Ameen San (17)

PLC Timers
PLC TimersPLC Timers
PLC Timers
 
PLC Internal Relays
PLC Internal RelaysPLC Internal Relays
PLC Internal Relays
 
PLC Intro to programming
PLC Intro to programmingPLC Intro to programming
PLC Intro to programming
 
PLC Logic Circuits
PLC Logic CircuitsPLC Logic Circuits
PLC Logic Circuits
 
PLC Applications
PLC ApplicationsPLC Applications
PLC Applications
 
Protection Devices and the Lightning
Protection Devices and the LightningProtection Devices and the Lightning
Protection Devices and the Lightning
 
Protection
ProtectionProtection
Protection
 
Circuit Breakers
Circuit BreakersCircuit Breakers
Circuit Breakers
 
Ratio analysis
Ratio  analysisRatio  analysis
Ratio analysis
 
Depreciation methods
Depreciation methodsDepreciation methods
Depreciation methods
 
Income statement
Income statementIncome statement
Income statement
 
Capital budgeting
Capital budgetingCapital budgeting
Capital budgeting
 
Time value of money
Time value of moneyTime value of money
Time value of money
 
Cash flow statement
Cash flow statementCash flow statement
Cash flow statement
 
Forms of business organizations
Forms of business organizationsForms of business organizations
Forms of business organizations
 
مهارات الحوار والاقناع
مهارات الحوار والاقناعمهارات الحوار والاقناع
مهارات الحوار والاقناع
 
Matlab solving rlc circuit
Matlab solving rlc circuitMatlab solving rlc circuit
Matlab solving rlc circuit
 

Kürzlich hochgeladen

CCS355 Neural Networks & Deep Learning Unit 1 PDF notes with Question bank .pdf
CCS355 Neural Networks & Deep Learning Unit 1 PDF notes with Question bank .pdfCCS355 Neural Networks & Deep Learning Unit 1 PDF notes with Question bank .pdf
CCS355 Neural Networks & Deep Learning Unit 1 PDF notes with Question bank .pdfAsst.prof M.Gokilavani
 
An introduction to Semiconductor and its types.pptx
An introduction to Semiconductor and its types.pptxAn introduction to Semiconductor and its types.pptx
An introduction to Semiconductor and its types.pptxPurva Nikam
 
Work Experience-Dalton Park.pptxfvvvvvvv
Work Experience-Dalton Park.pptxfvvvvvvvWork Experience-Dalton Park.pptxfvvvvvvv
Work Experience-Dalton Park.pptxfvvvvvvvLewisJB
 
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube Exchanger
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube ExchangerStudy on Air-Water & Water-Water Heat Exchange in a Finned Tube Exchanger
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube ExchangerAnamika Sarkar
 
Instrumentation, measurement and control of bio process parameters ( Temperat...
Instrumentation, measurement and control of bio process parameters ( Temperat...Instrumentation, measurement and control of bio process parameters ( Temperat...
Instrumentation, measurement and control of bio process parameters ( Temperat...121011101441
 
Sachpazis Costas: Geotechnical Engineering: A student's Perspective Introduction
Sachpazis Costas: Geotechnical Engineering: A student's Perspective IntroductionSachpazis Costas: Geotechnical Engineering: A student's Perspective Introduction
Sachpazis Costas: Geotechnical Engineering: A student's Perspective IntroductionDr.Costas Sachpazis
 
UNIT III ANALOG ELECTRONICS (BASIC ELECTRONICS)
UNIT III ANALOG ELECTRONICS (BASIC ELECTRONICS)UNIT III ANALOG ELECTRONICS (BASIC ELECTRONICS)
UNIT III ANALOG ELECTRONICS (BASIC ELECTRONICS)Dr SOUNDIRARAJ N
 
What are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptxWhat are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptxwendy cai
 
Past, Present and Future of Generative AI
Past, Present and Future of Generative AIPast, Present and Future of Generative AI
Past, Present and Future of Generative AIabhishek36461
 
Risk Assessment For Installation of Drainage Pipes.pdf
Risk Assessment For Installation of Drainage Pipes.pdfRisk Assessment For Installation of Drainage Pipes.pdf
Risk Assessment For Installation of Drainage Pipes.pdfROCENODodongVILLACER
 
Correctly Loading Incremental Data at Scale
Correctly Loading Incremental Data at ScaleCorrectly Loading Incremental Data at Scale
Correctly Loading Incremental Data at ScaleAlluxio, Inc.
 
Concrete Mix Design - IS 10262-2019 - .pptx
Concrete Mix Design - IS 10262-2019 - .pptxConcrete Mix Design - IS 10262-2019 - .pptx
Concrete Mix Design - IS 10262-2019 - .pptxKartikeyaDwivedi3
 
Artificial-Intelligence-in-Electronics (K).pptx
Artificial-Intelligence-in-Electronics (K).pptxArtificial-Intelligence-in-Electronics (K).pptx
Artificial-Intelligence-in-Electronics (K).pptxbritheesh05
 
Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024hassan khalil
 
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...srsj9000
 
Churning of Butter, Factors affecting .
Churning of Butter, Factors affecting  .Churning of Butter, Factors affecting  .
Churning of Butter, Factors affecting .Satyam Kumar
 

Kürzlich hochgeladen (20)

CCS355 Neural Networks & Deep Learning Unit 1 PDF notes with Question bank .pdf
CCS355 Neural Networks & Deep Learning Unit 1 PDF notes with Question bank .pdfCCS355 Neural Networks & Deep Learning Unit 1 PDF notes with Question bank .pdf
CCS355 Neural Networks & Deep Learning Unit 1 PDF notes with Question bank .pdf
 
An introduction to Semiconductor and its types.pptx
An introduction to Semiconductor and its types.pptxAn introduction to Semiconductor and its types.pptx
An introduction to Semiconductor and its types.pptx
 
Work Experience-Dalton Park.pptxfvvvvvvv
Work Experience-Dalton Park.pptxfvvvvvvvWork Experience-Dalton Park.pptxfvvvvvvv
Work Experience-Dalton Park.pptxfvvvvvvv
 
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube Exchanger
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube ExchangerStudy on Air-Water & Water-Water Heat Exchange in a Finned Tube Exchanger
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube Exchanger
 
Instrumentation, measurement and control of bio process parameters ( Temperat...
Instrumentation, measurement and control of bio process parameters ( Temperat...Instrumentation, measurement and control of bio process parameters ( Temperat...
Instrumentation, measurement and control of bio process parameters ( Temperat...
 
Sachpazis Costas: Geotechnical Engineering: A student's Perspective Introduction
Sachpazis Costas: Geotechnical Engineering: A student's Perspective IntroductionSachpazis Costas: Geotechnical Engineering: A student's Perspective Introduction
Sachpazis Costas: Geotechnical Engineering: A student's Perspective Introduction
 
UNIT III ANALOG ELECTRONICS (BASIC ELECTRONICS)
UNIT III ANALOG ELECTRONICS (BASIC ELECTRONICS)UNIT III ANALOG ELECTRONICS (BASIC ELECTRONICS)
UNIT III ANALOG ELECTRONICS (BASIC ELECTRONICS)
 
What are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptxWhat are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptx
 
Past, Present and Future of Generative AI
Past, Present and Future of Generative AIPast, Present and Future of Generative AI
Past, Present and Future of Generative AI
 
9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf
9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf
9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf
 
Risk Assessment For Installation of Drainage Pipes.pdf
Risk Assessment For Installation of Drainage Pipes.pdfRisk Assessment For Installation of Drainage Pipes.pdf
Risk Assessment For Installation of Drainage Pipes.pdf
 
Correctly Loading Incremental Data at Scale
Correctly Loading Incremental Data at ScaleCorrectly Loading Incremental Data at Scale
Correctly Loading Incremental Data at Scale
 
Concrete Mix Design - IS 10262-2019 - .pptx
Concrete Mix Design - IS 10262-2019 - .pptxConcrete Mix Design - IS 10262-2019 - .pptx
Concrete Mix Design - IS 10262-2019 - .pptx
 
Artificial-Intelligence-in-Electronics (K).pptx
Artificial-Intelligence-in-Electronics (K).pptxArtificial-Intelligence-in-Electronics (K).pptx
Artificial-Intelligence-in-Electronics (K).pptx
 
Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024
 
🔝9953056974🔝!!-YOUNG call girls in Rajendra Nagar Escort rvice Shot 2000 nigh...
🔝9953056974🔝!!-YOUNG call girls in Rajendra Nagar Escort rvice Shot 2000 nigh...🔝9953056974🔝!!-YOUNG call girls in Rajendra Nagar Escort rvice Shot 2000 nigh...
🔝9953056974🔝!!-YOUNG call girls in Rajendra Nagar Escort rvice Shot 2000 nigh...
 
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
 
Churning of Butter, Factors affecting .
Churning of Butter, Factors affecting  .Churning of Butter, Factors affecting  .
Churning of Butter, Factors affecting .
 
Design and analysis of solar grass cutter.pdf
Design and analysis of solar grass cutter.pdfDesign and analysis of solar grass cutter.pdf
Design and analysis of solar grass cutter.pdf
 
POWER SYSTEMS-1 Complete notes examples
POWER SYSTEMS-1 Complete notes  examplesPOWER SYSTEMS-1 Complete notes  examples
POWER SYSTEMS-1 Complete notes examples
 

Application of Capacitors to Distribution System and Voltage Regulation

  • 1. Chapter V Application of Capacitors to Distribution System and Voltage Regulation
  • 2. POWER FACTOR IMPROVEMENT Introduction: • The electrical energy is almost exclusively generated, transmitted and distributed in the form of alternating current. Therefore, the question of power factor immediately comes into picture. M • Most of the loads (e.g. induction motors , arc lamps) are inductive in nature and hence have low lagging power factor. The low power factor is highly undesirable as it causes an increase in current, resulting in an additional losses of active power in all the elements of power system from power station generator down to the utilization device. • In order to ensure most favourable conditions for a supply system from engineering and economical standpoint , it is important to have power factor as close to unity as possible.
  • 3. The cosine of angle between voltage and currentin an a.c. circuit is known as power factor.
  • 5.
  • 6. Disadvantages of Low Power Factor
  • 7.
  • 8.
  • 11.
  • 12.
  • 13. Calculations of Power Factor correction
  • 14.
  • 15. Nomogram for calculating Multiplication factor
  • 16. Problem A single phase motor connected to 400 V, 50 Hz supply takes 31·7A at a power factor of 0·7 lagging. Calculate the capacitance required in parallel with the motor to raise the power factor to 0·9 lagging.
  • 17. A 3-phase, 5 kW induction motor has a p.f. of 0·75 lagging. A bank of capacitors is connected in delta across the supply terminals and p.f. raised to 0·9 lagging. Determine the kVAR rating of the capacitors connected in each phase.
  • 18. Problem: The load on an installation is 800 kW, 0·8 lagging p.f. which works for 3000 hours per annum. The tariff is Rs 100 per kVA plus 20 paise per kWh. If the power factor is improved to 0·9 lagging by means of loss-free capacitors costing Rs 60 per kVAR, calculate the annual saving effected. Allow 10% per annum for interest and depreciation on capacitors.
  • 19.
  • 20. The operating power from distribution system is composed of both active and reactive elements. The typical daily load curves (reactive and active power) for a 66kV feeder is given in Fig. Real and Reactive Power Demand
  • 21. The reactive power is consumed by overhead lines, transformers and loads. Its proper generation and control is important for maintaining the network voltage under normal and abnormal power system operation and to reduce system losses. The system voltage collapse due to lack of global control of reactive power flow during crucial grid has collapsed many times during the past few years due to lack of reactive power in the region. Cost per kVAr of reactive power generation varies between 2 per cent and 4 per cent of per kW installed regulating controls. The system should be planned for carrying out suitable proportion of reactive energy.
  • 22. Reactive Power Consumption by lines: •The distribution lines consume reactive power (I2X) depending upon the series reactance (X) and load current (I). The series reactance of line is proportional to the conductor self – inductance, which decreases as the spacing between conductors decreases. •The minimum spacing is kept such as to prevent flash- over in foul weather conditions. According to a study of rural area , the average reactive power consumed by primary HT (11kV) and LT lines for each transformer at full-load is almost 1 per cent of transformer rating. The underground cable (11 kV and above) generate reactive power (Ic 2Xc) depending upon the capacitive reactance (Xc) and charging current (Ic) at rated voltage.
  • 23. Reactive Power Consumption by lines: •Increasing the line voltage at transformer and motors above the rated voltage will increase the consumption of reactive energy, the extent of which depends upon their designs. Generally, increase of 10% of the rated voltage will result in about 20% reduction of power factor.
  • 24. Reactive Power Consumption by Distribution Transformers The reactive power consumption takes place in the series leakage and the shunt magnetizing reactances. The second component is voltage dependent, while the first component is proportional to the square of the transformer current. A completely unloaded transformer would be very inductive and has a very low power factor. The reactive power used by a transformer (up to 100 kVA capacity) at full load and at rated voltage is approximately 7-9 % of the rated power of the transformer. When unloaded, the amount of reactive power remains between 3 and 4 % of the rated power.
  • 25. Reactive Power Consumption by Loads Loads have varying reactive power requirement. The low power factor can be a result of the equipment as in case of welders, or it can result from the operating conditions under which equipment is used as lightly loaded transformers and lightly loaded induction motors.
  • 26. Reactive Power Compensation and Voltage control Mainly capacitors are used to develop reactive power near the point of consumption. For capacitor compensation at load, the user reaps the same advantage as the power utility for higher power factor on small scale. Also, if each load is compensated, the power factor remains relatively constant since in plants, loads are switched on and off and the dangers of over – compensation do not exist. Suitable capacitor banks at grid or main sub- station are desirable to feed reactive requirement of lines, transformers and domestic consumers, etc., who have no capacitors at terminals.
  • 27. Over Compensation At the point of capacitors over-compensation, the voltage rises and capacitive kVAr will export, i.e. it will flow to reverse side of the load. Under certain conditions, dangerously high transient voltage may prevail on the power lines. Also, torque surges of over 20 times the motor rating can be transmitted to the motor shaft under rapid restart conditions. Over-compensation at consumer premises is not generally desirable.
  • 29. The minimum capacitor size can be connected permanently on secondary terminals, irrespective of load. This is the value of capacitance required to compensate the no-load magnetizing kV A of the transformer. Transformer KVA * % Impedance Minimum Capacitor in KVAr = _______________________________ 200
  • 30. Typical scheme for automatic control of LT capacitors at distribution transformers
  • 31. The minimum number of units required to limit the voltage increase to 10% can be calculated from the following equation for the grounded star bank. Where N = Minimum number of parallel units in one series section S = Number of series sections in each phase.
  • 32. System Harmonics With the increasing use of rectifiers, thyristor control shunt capacitors, etc. the harmonic generation can create problems with sensitive electronic equipment which can lead to errors in the protective gear, metering and control systems and also overload the capacitor banks besides causing resonance. Reactors are sometimes needed to reduce the total current drawn by the capacitor banks if unduly large harmonics are present in the system voltage.
  • 33. The causes of harmonics in the power system • Over-excited transformers • Mercury rectifiers and thyristors • Arc furnaces • Slot harmonics of rotary machine • Corona loss • Large motors running at low slip, fluorescent lighting , T.V. and radio equipment • System switching and load chocking
  • 34. Inrush Currents When the capacitor banks are connected parallel to the supply, the initial charging current is said be inrush current. The inrush current can be reduced by connecting the series damping reacors. In the case of single capacitor bank, the damping reactor is not normally required from the consideration of inrush currents at the time of switching. The system reactance including the transformer to which the capacitor bank is installed is adequate enough to bring down the value of inrush currents with in safe limit of the capacitor or switchgear. Even otherwise the duration of inrush current is so small , of the order of few cycles only, that their effect can be ignored. When a number of capacitor banks are used in parallel, it may become necessary to use series reactors for limiting the inrush currents.
  • 35. Assuming the severest condition of switching , the value of damping reactors in henries is given by
  • 36. The maximum peak inrush current can be approximately given by the formula Where, Ic1 = capacitor’s rated current (fundamental wave) rms Xc1 = capacitor reactance (fundamental wave) Xl1 = total inductive reactance of the system including capacitor bank (fundamental wave)
  • 37.
  • 38. In case of parallel banks, which are already energized, the inrush current is predominantly governed by the momentary discharge from the energized banks and since the impedance between the energized capacitor bank and the capacitor bank to be energized may be small, it may result in high peak inrush current. The maximum peak current is given by the expression C= equivalent capacitance of the circuit in H L= equivalent series inductance between the energized banks and bank to be energized in H En1 = line to neutral voltage
  • 39. Example Two 11 kV capacitors banks, each of 2.5 MVAr, are installed in parallel at a 132/11 kV sub-station. Calculate the value of the series damping reactor with each capacitor bank
  • 41. Load Utilized Voltage 10 kW 230 V 10-50 kW 415/230 V 50 kW-5 MW 11 kV 5 MW-30 MW 33-66 kV 30 MW-50MW 132 kV Above 50 MW 220 kV Different Consumers Voltage Standards
  • 43.
  • 45. Importance Of Voltage Control When the load on the supply system changes, the voltage at the consumers' terminals also changes. The variations of voltage at the consumer's terminals are undesirable and must be kept within prescribed limits for the following reasons :
  • 46. (i) In case of lighting load, the lamp characteristics are very sensitive to changes of voltage. For instance, if the supply voltagip to an incandescent lamp decreases by 6% of rated value, then illuminating power may decrease by 20%. On the other hand, if the supply voltage is 6% above the rated value, the life of the lamp may be reduced by 50% due to the rapid deterioration of the filament.
  • 47. (ii) In case of power load consisting of induction motors, the voltage variations may cause erratic operation. If the supply voltage is above the normal, the motor may operate with a saturated magnetic circuit, with consequent large magnetising current, heating and low power factor. On the other hand, if the voltage is too low, it will reduce the starting torque of the motor considerably.
  • 48. (iii) Too wide variations of voltage cause excessive heating of distribution transformers. This may reduce their ratings to a considerable extent.
  • 49. It is clear from the above discussion that voltage variations in a power system must be kept to minimum level in order to deliver good service to the consumers. With the trend towards larger and larger interconnected system, it has become necessary to employ appropriate methods of voltage control.
  • 50. Methods Of Voltage Control There are several methods of voltage control. In each method, the system voltage is changed in accordance with the load to obtain a fairly constant voltage at the consumer's end of the system. The following are the methods of voltage control in an a.c. power system: (i) By excitation control (ii) By using tap changing transformers (iii) Auto-transformer tap changing (iv) Booster Transformers (v) Induction Regulators (vi) By Synchronous Condensors
  • 51. Method (i) is used at the generating station only whereas methods (ii) to (v) can be used for transmission as well as primary distribution systems. However, method
  • 52. Tap-Changing Transformers Off load tap-changing transformer
  • 53.
  • 54. Figure shows the arrangement where a number of tappings have been provided on the secondary. As the position of the tap is varied, the effective number of secondary turns is varied and hence the output voltage of the secondary can he changed.
  • 55. Thus referring to Fig. when the movable arm makes contact with stud 1, the secondary voltage is minimum and when with stud 5, it is maximum. During the period of light load, the voltage across the primary is not much below the alternator voltage and the movable arm is placed on stud 1. When the load increases,
  • 56. the voltage across the primary drops, but the secondary voltage can be kept at the previous value by placing the movable arm on to a higher stud. Whenever a tapping is to be changed in this type of transformer, the load is kept off and hence the name off load tap. changing transformer
  • 57.
  • 58. ON load tap-changing transformer