14. Selection of Detectors for different Area S.No PLANT AREA TYPE OF DETECTORS 1. Main control room, Computer room, Electronic cubicle room and control rooms in outlying areas. Combination of - Ionisation smoke detector Optical type smoke detector 2. Switchgear rooms in main Plant and outlying areas, battery charger room, record and shift-in-charge engineers room Ionisation type smoke detector. 3. Office rooms / storage rooms Ionisation type smoke detector 4. Battery rooms and chemically corrosive areas. Corrosion resistant, Rate of rise of temperature heat detector with fixed temperature setting. 5. Cable gallery Combination of Optical type smoke detectors and Linear heat sensor running above all HV and LV power cable trays. Unless the vertical distance between cable tray is less than 500 mm in which case alternate trays (in addition to the top and bottom trays). The optical smoke detector and LHS detectors along with necessary number of interface units in the cable gallery will be cross zoned to actuate the water spray system 6. Station building / Plant area Infrared flame detectors (where oil tanks are located), spray tanks rate of rise of temp. detector with fixed element
15. 7. Coal Conveyors Analogue Linear heat sensor cable, infra red spark / ember detectors and manual call points . If water spray system is provided the LHS cable and IR detector will be cross zoned to actuate the same 8. Dusty areas in coal handling plants like crusher house Flame proof manual call points 9. Junction towers Flame proof heat detectors, flame proof manual call points 10. Conveyor tunnels Flame proof infrared detectors, flame proof MCPs , LHS cables 11. Hazardous plant areas such as fuel oil / lube oil, DG houses, H 2 generating plants and hydrogen storage areas. Flame proof rate of rise of temperature detector with fixed element and flame proof MCP