This document provides an overview of HVAC distribution systems for a class on HVAC system design. It discusses various types of distribution systems including single zone, constant volume, VVT, VAV reheat, dual duct, DOAS, displacement, UFAD and natural ventilation. For each type, it highlights reasons for choosing the system and potential limitations. It also outlines the course topics to be covered by three instructors over 10 classes, and provides examples of different distribution system layouts.
Incoming and Outgoing Shipments in 3 STEPS Using Odoo 17
2015 x472 class 03 - distribution systems
1. X472 HVAC System Design
Considerations
Class 3 – Distribution Systems
Todd Gottshall, PE
Western Allied
Redwood City, CA
Reinhard Seidl, PE
Taylor Engineering
Alameda, CA
Fall 2015
Mark Hydeman, PE
Continual
San Francisco, CA
2. 2
General
Contact Information
Reinhard: rseidl@taylor-engineering.com
Mark: mhydeman@continual.net
Todd: tgottshall@westernallied.com
Text
• None
Slides
• download from web before class
• Log in to Box at https://app.box.com/login
• Username: x472student@gmail.com
• Password: x472_student (case sensitive)
3. 3
Course Outline
Date Class Topic Teacher
9/02/2015 1. Introduction / Systems Overview / walkthrough RS
9/09/2015 2. Generation Systems TG
9/16/2015 3. Distribution Systems RS
9/23/2015 4. Central Plants TG
9/30/2015 5. System Selection 1 - class exercises RS
10/07/2015 6. Specialty Building types (High rise, Lab, Hospital,
Data center)
TG
10/14/2015 7. System Selection 2 - class exercises RS
10/21/2015 8. Construction codes and Project delivery methods TG
10/28/2015 9. 2013 T24 and LEED v4 MH
11/04/2015 10. Life-Cycle Cost Analysis and exam hand-out TG
There are three instructors for this class. Todd Gottshall (TG), Reinhard Seidl (RS)
and Mark Hydeman (MH). The schedule below shows what topics will be covered by
who, and in what order.
4. 4
Birds Eye View of Systems
Single Story – tilt-up
• Single zone rooftop AC
• Split units, VRV
Two-Story
• Single zone rooftop AC
• Multi-zone rooftop AC
3-8 Story
• Centralized systems
• Dual Duct
• VAV RH
High-rise
• Floor-by-floor
• Built-up Systems
• Condenser loops, tenant heat
pumps
Campus Systems
• Central plant, airside/water
side economizers, thermal
energy storage
• Cogeneration
Specialty Systems
• Hotel
• Library
• Laboratory
• Underfloor
• Natural Ventilation
• Direct/Indirect
• Cascading cooling towers
6. 6
Distribution Systems
Single zone
Zoned, but constant volume
VVT
VAV Reheat
Dual Duct (single fan, dual fan)
DOAS (Dedicated Outside Air System) with
auxiliary cool/heat from
• Fancoil, WSHP, Induction unit, Radiant
Displacement
UFAD
Natural Ventilation
8. 8
Single Zone
Why choose single zone ?
• Cheap
• Simple
• Provides fairly good temperature zones
Why Not ?
• Doesn’t work well for multi-story buildings
because of multiple shafts
9. 9
Distribution Systems
Single zone
Zoned, but constant volume
VVT
VAV Reheat
Dual Duct (single fan, dual fan)
DOAS (Dedicated Outside Air System) with
auxiliary cool/heat from
• Fancoil, WSHP, Induction unit, Radiant
Displacement
UFAD
Natural Ventilation
11. 11
Single Zone
Why choose CV reheat ?
• May be needed for pressurization
• Used to be a common system because
controls hadn’t been developed
• Can be used in DOAS systems (dedicated
outside air) such as induction unit systems
Why Not ?
• Very energy inefficient when used other
than for DOAS
12. 12
Distribution Systems
Single zone
Zoned, but constant volume
VVT
VAV Reheat
Dual Duct (single fan, dual fan)
DOAS (Dedicated Outside Air System) with
auxiliary cool/heat from
• Fancoil, WSHP, Induction unit, Radiant
Displacement
UFAD
Natural Ventilation
13. 13
VVT System Requires a Bypass
If we vary airflow on a constant volume unit we have too
little airflow on a constant volume system = frozen unit
Frozen
compressor,
suction line
Frozen
evaporator
14. 14
VVT System
Until very recently, could not get
systems with low tonnage (< 10 tons
or so) with variable speed drive
Had to use bypass damper instead
Note: recently, thanks to “digital
scroll”, small tonnage VAV units have
started to appear.
15. 15
VVT System
New 2013 T24 requires small tonnage
units to be multi-stage
See http://www.energy.ca.gov/title24/2013standards/index.html
Prescriptive requirements section
140.4.m (fan speed control) and
section 140.4.e.5 (compressor stages)
as part of economizer requirements
19. 19
VVT System
Why choose VVT ?
• Better control than constant volume single zone, but
not as good as “real” VAV
• Flexible zoning
• Zoning can change with churn
• Fits into tighter ceiling space than dual duct
Why Not ?
• Users sometimes misunderstand what they’re getting
– comfort will never equal a VAV reheat or Dual Duct
system
• Cannot zone across very different load patterns
(example: can’t use one package unit with VVT to
cover an East and a North exposure)
20. 20
Distribution Systems
Single zone
Zoned, but constant volume
VVT
VAV Reheat
Dual Duct (single fan, dual fan)
DOAS (Dedicated Outside Air System) with
auxiliary cool/heat from
• Fancoil, WSHP, Induction unit, Radiant
Displacement
UFAD
Natural Ventilation
26. 26
VAV Reheat
Why choose VAV Reheat ?
• Good control for multiple floors
• Flexible
• Zoning can change with churn
• Fits into tighter ceiling space than dual duct
Why Not ?
• More expensive than single zone
• Re-heats
• Typically less energy efficient than dual duct
27. 27
Air Terminal Unit (CAV or
VAV Box)
AFS=Automatic Flow Station
Works on same principle as Pitot tube
Damper controls typically pneumatic,
Electronic (stand-alone) or DDC (networked)
29. 29
VAV Reheat
Problem with reheat ?
• Just that. Reheat means destroying energy:
• First cool the air
• Then heat it back up
• You pay 2x
• Code (CA Title 24) limits the amount of reheat you can
do (see section on dual max control T24, 140.4.d)
What alternatives ?
• Use fan-powered terminals
• Provide heating by heating space air, not primary
supply air (in some ways, this is what a good dual duct
design does)
30. 30
VAV Box Minimums (from
Title-24)
Reheat, T24 allows maximum of (with
DDC control):
• 20% of design cooling airflow
• ventilation requirements (see below)
Ventilation Minimum Requirement =
Maximum of:
• 0.15 CFM/square foot
• 15 CFM/person
33. 33
VAV Reheat
Series fan-powered
• Constant volume system
• Fan has to run when occupied
• Reduces central system fan static somewhat
Parallel fan-powered
• System works with or without fan
• Fan comes on only for heating
• More energy efficient than series type
36. 36
Distribution Systems
Single zone
Zoned, but constant volume
VVT
VAV Reheat
Dual Duct (single fan, dual fan)
DOAS (Dedicated Outside Air System) with
auxiliary cool/heat from
• Fancoil, WSHP, Induction unit, Radiant
Displacement
UFAD
Natural Ventilation
38. 38
Dual-Duct VAV
Why choose dual duct ?
• More energy efficient (no reheat)
• Good zoning
• Zoning can change with churn
Why Not ?
• On systems with lots of outside air (school,
assembly), benefit of not re-heating is lost
• May not fit in ceiling space
• Depending on labor rates, may be more expensive
than reheat system
• More rooftop equipment
42. 42
Dual-Duct VAV Box
DD terminals often feature a mixing
plenum at the outlet to prevent cold
air going one way, and hot air going
the other way
DD is harder to
route through a
building than a
VAV reheat
system!
43. 43
Distribution Systems
Single zone
Zoned, but constant volume
VVT
VAV Reheat
Dual Duct (single fan, dual fan)
DOAS (Dedicated Outside Air System) with
auxiliary cool/heat from
• Fancoil, WSHP, Induction unit, Radiant
Displacement
UFAD
Natural Ventilation
45. 45
Induction Units and Fancoil
Units
Note: when laying out
piping, consider the
H/W ratio of the building
to figure out whether it
is more cost effective to
run multiple risers with
short branches, or
fewer risers with longer
branches.
It’s easy to figure out,
just make a
spreadsheet with linear
feet of piping.
This is equally true for
VAV reheat piping
loops, and condenser
water loops for
WSHP’s.
One building facade Piping option 1 Piping option 2 ….. Piping option x
46. 46
DOAS: Floor-by-floor units
One mech. Room per floor, one large heat pump
Boiler for
VAV
Reheat
Elevator
machine
room unit
Cooling
Towers
Makeup Air
Handler
47. 47
DOAS
Why choose DOAS system ?
• Small ductwork, small OA air handlers
• Easy calculation/control of ventilation
requirements
• Flexible
Why Not ?
• Fairly expensive (many terminal units or
radiant panels)
• No airside economizer (big hit for Bay Area,
small hit for Florida)
48. 48
DOAS: Induction Units
Why choose Induction units/chilled beams ?
• No fan (no electrical at all in pneumatic control option)
• Small zones, individual control
• Low noise
Why Not ?
• Very expensive (see article from May 2013)
• High static on DOAS fans (although much better in modern
chilled beam design) and constant volume, leading to high
annual fan power
• Noise (also better on modern designs)
• Older vertical units: high maintenance/hard to clean, loss of
capacity when carpet particles in coil reduce or eliminate
induction
49. 49
DOAS: Induction Systems
Actually a re-cooling system, not
re-heating system: in winter,
outside air handler provides hot air
(hot enough for all zones). The
overheated zones are re-cooled
by the induction units.
51. 51
DOAS: Induction Systems
Induction units are often a maintenance problem, because when dirt accumulates in the coil,
there is very little static pressure from the induction effect. Unless coils stay clean, induced air
volume is reduced over time, until the units don’t cool effectively.
54. 54
DOAS: Fancoil Unit
Unlike induction units, fancoils actively push air through the cooling coil and
have much more “motive force” to ensure that coil flow remains as designed.
55. 55
DOAS: Fancoil units
Why choose Fancoil units ?
• Flexible
• Small zones, individual control
• High local capacity
Why Not ?
• Fairly expensive
• No airside economizer
• Possible leaks (for IDF/Data rooms)
56. 56
DOAS: Fancoil Unit
High Internal loads,
quiet operation:
Chilled-water fancoil
Note spring isolation
hangers
57. 57
DOAS: WSHP
Why choose water-source heat pumps ?
• Flexible
• Small zones, individual control
• High local capacity
• Cool/heat on one circuit (uninsulated condenser water)
• Lower first cost than fancoil system
• Recover heat during simultaneous heating and cooling
Why Not ?
• More expensive units (each has its own compressor)
• More maintenance intensive than fancoils
• Noisier than fancoils
• No airside economizer
58. 58
DOAS: WSHP
Like fancoils, WSHP units can handle localized loads. They use condenser water (for heating and
cooling) instead of chilled water and hot water.
59. 59
DOAS: WSHP
Unlike fancoils, WSHP units are harder to maintain, since they have many more parts – in particular,
they contain a compressor (often 207V or 480V) and a condenser, plus a control panel.
A fancoil contains just a fan (usually 120V) and a coil.
60. 60
DOAS: Radiant Systems
Why choose Radiant Systems ?
• Quiet (No noise)
• Energy efficient
• High comfort level
Why Not ?
• Can be expensive (panels much more so than in-floor
piping)
• Fairly limited capacity (this determines cost – if
additional systems are needed to augment capacity,
then overall solution becomes expensive)
• Controllability: slow reaction (Panels faster than floor)
• Architectural integration
62. 62
DOAS: Radiant Systems
Zoning works by providing
a piping header that feeds
several loops with control
valves.
Exterior areas may have
denser pipe spacing, and
different zoning than
interior zones.
As with underfloor (UFAD)
systems, zones tend to be
quite large.
64. 64
DOAS: Radiant Systems
Zoning works by providing
a piping header that feeds
several loops with control
valves.
Shown on the left is a
distribution header for one
zone, the individual pipes
are equipped with circuit
setters.
The entire heater will have
one temperature control
valve.
69. 69
Distribution Systems
Single zone
VVT
VAV Reheat
Dual Duct (single fan, dual fan)
DOAS (Dedicated Outside Air System)
with auxiliary cool/heat from
• Fancoil, WSHP, Induction unit, Radiant
Displacement
UFAD
Natural Ventilation
71. 71
Displacement Ventilation
As air rises, it creates a natural
convection draft that pulls in cool
air from below. Cool air “finds its
own way to the load”
72. 72
Displacement Systems
Why choose Displacement Systems ?
• Work in large areas without duct distribution
• Handle the load where it occurs
• Natural stratification
Why Not ?
• Small spaces
Individual drops (for duct from overhead) per space
Large supply openings
• High loads (can’t supply air very cold because of
discomfort).
• No Heating!
75. 75
Distribution Systems
Single zone
VVT
VAV Reheat
Dual Duct (single fan, dual fan)
DOAS (Dedicated Outside Air System)
with auxiliary cool/heat from
• Fancoil, WSHP, Induction unit, Radiant
Displacement
UFAD
Natural Ventilation
78. 78
Underfloor Air Distribution
Systems
Weaknesses : Unknown effects: Note: our experience by now shows that stratification works less
well than expected, that the air warms up under the floor, reducing the low DT and extended
economizer use, and that air distribution suffers from leakage in the real world.
Return Air Grille
Raised Access Floor
Return Air Plenum
Ceiling
Tset
Qoccupied
Qstratified
CFM, Tsupply
Treturn
82. 82
Underfloor Air Distribution
Systems
Weaknesses : Accessibility for
underfloor terminals
Terminals are fancoils or fan-
powered terminals for high-load
exterior spaces, and are ducted
like regular fancoils
83. 83
Underfloor Air Distribution
Systems
Weaknesses : underfloor distribution
Despite the pressurized plenum, it becomes
necessary to run underfloor “air highways” to
direct the air and counter effects of large
swirls, turbulence and the like, that cause
“mysterious” temperature fluctuations.
These are especially hard to seal unless
made just like ducts.
85. 85
Underfloor Air Distribution
Systems
Why choose UFAD Systems ?
• Work in large areas without duct distribution
• Handle the load where it occurs
• Natural stratification
• Low fan pressures, lower DT, better economizer use
Why Not ?
• Small spaces
• Large floor plates (air heats up underfloor)
• Sealing of plenum is difficult, leads to problems for
operation
86. 86
Distribution Systems
Single zone
VVT
VAV Reheat
Dual Duct (single fan, dual fan)
DOAS (Dedicated Outside Air System)
with auxiliary cool/heat from
• Fancoil, WSHP, Induction unit, Radiant
Displacement
UFAD
Natural Ventilation
87. 87
Natural Ventilation
Despite being many thousands of
years old, natural ventilation is now
in its infancy again.
Wind tunnel studies and/or CFD
calculations are usually required to
make buildings work in the design
phase.
Experiences from the real world are
beginning to increase, but are still
only a small fraction of commercial
buildings.
88. 88
Natural Ventilation
To determine the
shape of the building
overhangs for
shading, and location
for wind, you have to
start “from scratch”
89. 89
Natural Ventilation
Every aspect of the building
geometry affects airflows.
Thus, the architect is now as much
a mechanical designer as the
mechanical engineer – the shape of
the building, the walls, the windows,
all make up the mechanical system.
The mechanical engineer has to
review items such as windows as
part of the mechanical submittal
process !
98. 98
Natural Ventilation
Why choose Natural Ventilation Systems ?
• Energy Efficient
• Environmentally responsible
Why Not ?
• Complex, small reservoir of practical expertise
• Expensive (wind tunnel, CFD)
• Hard to fix if design flaws occur
• Requires whole new paradigm of coordination
between engineering team members