SlideShare a Scribd company logo
1 of 42
Internship Training Report
132kv Grid Substation Kamalabad, P&I
IESCO
by
Muhammad Usman Rafiq
F-4068
A Report submitted to the
Department of P&I, IESCO
Islamabad
in partial fulfillment of the requirements for the
internship of one month for
BACHELOR OF SCIENCE IN ELECTRICAL ENGINEERING
P&I, IESCO Islamabad, 46000 Pakistan
<August, 2016>
ii
Copyright ยฉ 2014 by APCOMS
All rights reserved. Reproduction in whole or in part in any form requires the prior
written permission of Muhammad Usman Rafiq or designated representative.
DEDICATION
Thanks to almighty Allah, who makes me, grows me and produces such abilities in me so I
become able to produce such report. I want to dedicate โ€œMy Little Workโ€ to my parents and
teachers. Parents and teachers have a great role in my life. Both the personalities exert a lot of
efforts on me which make me eligible for making this report.
C E R T I F I C A T E O F A P P R O
V A L
It is certified that the work of report titled โ€œ132K Internship Training Report
132kv Grid Substation Kamalabad, P&I IESCOโ€ is carried out by Muhammad Usman
Rafiq, Roll. No F-4068, under the supervision of IESCO, at Islamabad and
Rawalpindi. It is fully adequate, in scope and in quality, as a report for the internship
of one month.
Supervisor: ------------------------
ACKNOWLEDGMENT
IESCO has been the ideal training institute. Officials deputed are highly trained; their
sage advices, insightful criticisms, and patient encouragement aided this report in
innumerable ways. I would also like to thank trainers which steadfast support of this
report was greatly needed and deeply appreciated.
DECLARATION
We hereby declare that this project, neither as a whole nor as a part thereof has been
copied from any source. It is further declared that we have developed this report entirely
on the basis of our personal efforts under the sincere guidance of IESCO officials.
______________________
Muhammad Usman Rafiq
ABSTRACT
Now a dayโ€™s everything is depending up on the power. So give the reliable supply to the
consumers. In distribution systems one of the major parts is "SUBSTATIONS".
An electrical substation is a subsidiary station of an electricity, Generation, Transmission
and distribution systems where the voltage is transformed from high to low or reverse using
the transformers .Electric power may flow through several substations between generating
plant and consumer and may be changed in different voltage levels .the equipment used in
substation are Transformer, Lightening arresters, isolator, bus bar, protective devices,
Battery charger, earth switches, earth rods. So for of supply the regular maintenance and
checking is necessary from that we conclude weather it is suitable or not for the desired
operation.
TABLE OF CONTENTS
Chapter 1
Introduction ....................................................................... 8
1.1 Substation .................................................................... 8
1.2 132Kv single-line grid substation diagram ............................... 9
1.2 Classification of substation ...................................................... 10
1.3 Function of substation ................................................. 11
Chapter 2
Equipment Used in a Sub Station โ€ฆโ€ฆ.................................. 12
2.1 Transformer ...................................................................... 12
Types of transformer
2.1.1 Power Transformer ............................................. 12
2.1.1.1 Parts of transformer
1. Conservative Tank .................................. 14
2. Tape Changer .......................... 15
3. Buchholz Relay .......................... 16
4. Silica Gel .......................... 17
2.1.2 Instrument transformer ........................ 19
2.1.2.1 Current transformer ........................ 19
2.1.2.2 Potential transformer ........................ 20
2.1.2.3 Unit Auxiliary transformer ........................ 21
Chapter 3
Circuit Breaker โ€ฆโ€ฆโ€ฆโ€ฆ......................................................... 24
3.1 S F 6 g a s c i r c u i t b r e a k e r ........................... 24
Chapter 4
Bus Coupler ................................................... 27
4.1 Bus coupler ....................................... 27
Chapter 5
11kv incoming and outgoing Panels ................................................. 29
5.1 11kv incoming Panels .............................................................. 29
5.2 11kv outgoing Panels .............................................................. 31
Chapter 6
Batteries and Batteries Charger ................................................. 32
6.1 Station Batteries System ................................................. 32
Chapter 7
Electrical Function Numbers ............................................. 36
7.1 Introduction ................................................. 36
7.2 List of device numbers and acronyms ........................................ 36
7.3 Suffixes and prefixes
........................................ 39
CHAPTER 1
Introduction:
The present day electrical power system is a.c i.e. electric power is
generated, transmitted and distributed in the form of Alternating current. The
electric power is produce at the power station, which are located at favorable
places. It is delivered to the consumer through a large network of transmission
and distribution. At many place in the line of power system, it may be desirable
and necessary to change some characteristic ( e.g. Voltage, ac to dc, frequency
p.f. etc.) of electric supply. This is accomplished by suitable apparatus called
sub-station for example, generation voltage (11kv or 6.6kv) at the power station
is stepped up to high voltage (Say 220kv to 132kv) for transmission of electric
power. Similarly near the consumerโ€™s localities, the voltage may have to be
stepped down to utilization level. This job is again accomplished by suitable
apparatus called sub-stations.
1.1 Substation:
An electrical substation is a subsidiary station of an electricity
generation, transmission and distribution system where voltage is transformed
high to low or the reverse using transformers. Electric power may flow through
several substations between generation plant and consumer, and may be
changed in voltage in several steps.
The main equipment used in substation are transformers lighting
arresters, Circuit breakers PLCC, isolators, bus bars, protective relays, Battery
8
charger, earth switches, earth rods. .
9
1.2 Classification of substations:
Classification of substations based on
(1) Service requirements
(2) Constructional features
1. According to service requirements: According to service requirements
substations are classified into:
i. Transformer Substations
ii. Switching Substations
iii. Power factor correction substations
iv. Frequency changer substations
v. Converting substations
vi. Industrial substations
2. According to construction features: According to constructional features
substations are classified as;
i. Indoor substations
ii. Outdoor substations
iii. Underground substations
iv. Pole mounted substations
10
1.3 Functions of a Substation:
1 - Supply of required electrical power.
2 - Maximum possible coverage of the supply network.
3 - Maximum security of supply.
4 - Shortest possible fault-duration.
5 - Optimum efficiency of plants and the network.
6 - Supply of electrical power within targeted frequency limits, (49.5 Hz
and50.5 Hz).
7 - Supply of electrical power within specified voltage limits.
8 - Supply of electrical energy to the consumers at the lowest cost.
11
Chapter 2
Equipment Used in a Sub-Station
The equipment required for a transformer Sub-Station depends upon the
type of Sub-Station, Service requirement and the degree of protection desired.
TIF Sub-Station has the following major equipments.
2.1 Transformers:
Transformer is a static machine, which transforms the potential of
alternating current at same frequency. It means the transformer transforms the
low voltage into high voltage & high voltage to low voltage at same frequency.
It works on the principle of static induction principle.
When the energy is transformed into a higher voltage, the transformer is called
step up transformer but in case of other is known as step down transformer.
TYPES OF TRANSFORMERS
2.1.1 Power Transformer:
It is used for the transmission purpose at heavy load, high voltage
greater than 33 KV & 100% efficiency. It also having a big in size as compare
to distribution transformer, it used in generating station and Transmission
substation at high insulation level. They can be of two types: Single Phase
Transformers and Multi Phase Transformers.
12
13
Nameplate:
14
2.1.1.1 Parts of power transformer:
15
i. Conservator Tank:
This is a cylindrical tank mounted on supporting structure on the
roof the transformer main tank. The main function of conservator tank of
transformer is to provide adequate space for expansion of oil inside the
transformer.
Function of Conservator Tank of a Transformer:
When transformer is loaded and when ambient temperature rises,
the volume of oil inside transformer increases. A conservator tank of
transformer provides adequate space to this expanded transformer oil. It also
acts as a reservoir for transformer insulating oil.
Construction of Conservator Tank:
This is a cylindrical shaped oil container closed from both ends.
One large inspection cover is provided on either side of the container to
facilitate maintenance and cleaning inside of the conservator.
Conservator pipe, i.e. pipe comes from main transformer tank, is
projected inside the conservator from bottom portion. Head of the
conservator pipe inside the conservator is provided with a cap. This pipe is
projected as well as provided with a cap because this design prevents oil
sludge and sediment to enter into main tank from conservator. Generally
silica gel breather fixing pipe enters into the conservator from top. If it enters
from bottom, it should be projected well above the level of oil inside the
conservator. This arrangement ensures that oil does not enter the silica gel
breather even at highest operating level.
16
Working of Conservator Tank:
When volume of transformer insulating oil increases due to load
and ambient temperature, the vacant space above the oil level inside the
conservator is partially occupied by the expanded oil. Consequently,
corresponding quantity of air of that space is pushed away through breather.
On other hand, when load of transformer decreases, the transformer is
switched off and when the ambient temperature decreases, the oil inside the
transformer contracts. This causes outside air to enter in the conservator tank
of transformer through silica gel breather.
ii. Tape Changer:
A tap changer is a connection point selection mechanism along
a power transformer winding that allows a variable number of turns to be
selected in discrete steps. A transformer with a variable turns ratio is
produced, enabling stepped voltage regulation of the output. The tap
selection may be made via an automatic or manual tap changer mechanism.
17
Voltage considerations:
If only one tap changer is required, manually operated tap
points are usually made on the high voltage (primary) or lower current
winding of the transformer to minimize the current handling requirements
of the contacts. However, a transformer may include a tap changer on
each winding if there are advantages to do so. For example, in power
distribution networks, a large step-down transformer may have an off-
load tap changer on the primary winding and an on-load automatic tap
changer on the secondary winding or windings. The high voltage tap is
set to match long term system profile on the high voltage network
(typically supply voltage averages) and is rarely changed. The low
voltage tap may be requested to change positions multiple times each day,
without interrupting the power delivery, to follow loading conditions on
the low-voltage (secondary winding) network.
To minimize the number of winding taps and thus reduce the
physical size of a tap changing transformer, a 'reversing' tap changer
winding may be used, which is a portion of the main winding able to be
connected in its opposite direction (buck) and thus oppose the voltage.
iii. Buchholz Relay:
Buchholz relay in transformer is an oil container housed the
connecting pipe from main tank to conservator tank. It has mainly two
elements. The upper element consists of a float. The float is attached to a
hinge in such a way that it can move up and down depending upon the oil
level in the Buchholz relay Container. One mercury switch is fixed on the
float. The alignment of mercury switch hence depends upon the position
of the float.
The lower element consists of a baffle plate and mercury switch.
This plate is fitted on a hinge just in front of the inlet (main tank side) of
Buchholz relay in transformer in such a way that when oil enters in the
relay from that inlet in high pressure the alignment of the baffle plate
along with the mercury switch attached to it, will change.
18
In addition to these main elements a Buchholz relay has gas release
pockets on top. The electrical leads from both mercury switches are taken
out through a molded terminal block.
iv. Silica Gel Breather of Transformer:
Whenever electrical power transformer is loaded, the temperature of
the transformer insulating oil increases, consequently the volume of the oil is
increased. As the volume of the oil is increased, the air above the oil level in
conservator will come out. Again at low oil temperature; the volume of the oil is
decreased, which causes the volume of the oil to be decreased which again
causes air to enter into conservator tank.
The natural air always consists of more or less moisture in it and this
moisture can be mixed up with oil if it is allowed to enter into the transformer.
The air moisture should be resisted during entering of the air into the
transformer, because moisture is very harmful for transformer insulation. A
silica gel breather is the most commonly used way of filtering air from moisture.
Silica gel breather for transformer is connected with conservator tank by
means of breathing pipe.
19
Construction of Silica Gel Breather:
The silica gel breather of transformer is very simple in the aspect of
design. It is nothing but a pot of silica gel through which, air passes during
breathing of transformer. The silica gel is a very good absorber of moisture.
Freshly regenerated gel is very efficient, it may dry down air to a dew point of
below โˆ’40ยฐC. A well maintained silica gel breather will generally operate with a
dew point of โˆ’35ยฐC as long as a large enough quantity of gel has been used. The
picture shows a silica gel breather of transformer.
Working Principle of Silica Gel Breather:
Silica gel crystal has tremendous capacity of absorbing moisture. When
air passes through these crystals in the breather; the moisture of the air is
absorbed by them. Therefore, the air reaches to the conservator is quite dry, the
dust particles in the air get trapped by the oil in the oil seal cup. The oil in the
oil sealing cup acts as barrier between silica gel crystal and air when there is no
flow of air through silica gel breather. The color of silica gel crystal is dark blue
but, when it absorbs moisture; it becomes pink.
When there is sufficient difference between the air inside the conservator
and the outside air, the oil level in two components of the oil seal changes until
the lower oil level just reaches the rim of the inverted cup, the air then moves
from high pressure compartment to the low pressure compartment of the oil
20
seal. Both of these happen when the oil acts as core filter and removes the dust
from the outside air.
2.1.2 Instrument Transformers:
These transformers are used for the measurement purposes at that
points where standard voltmeters and ammeters cannot be used. They are of two
types:
2.1.2.1 CURRENT TRANSFORMER:
A current transformer (CT) is used
for measurement of alternating electric currents.
When current in a circuit is too high to apply
directly to measuring instruments, a current
transformer produces a reduced current accurately
proportional to the current in the circuit, which
can be conveniently connected to measuring and
recording instruments. A current transformer
isolates the measuring instruments from what
may be very high voltage in the monitored circuit.
Nameplate:
21
2.1.2.2 POTENTIAL OR VOLTAGE TRANSFORMER:
Voltage transformers (VT) (also called
potential transformers (PT)) are a parallel connected
type of instrument transformer, used for metering
and protection in high-voltage circuits or phase shift
isolation. They are designed to present negligible
load to the supply being measured and to have an
accurate voltage ratio to enable accurate metering. A
potential transformer may have several secondary
windings on the same core as a primary winding, for
use in different metering or protection circuits.
Nameplate:
22
2.1.2.3 Unit Auxiliary Transformers (UAT)
The Unit Auxiliary Transformer is the Power Transformer that
provides power to the auxiliary equipment of a power generating station during
its normal operation. This transformer is connected directly to the generator out-
put by a tap-off of the isolated phase bus duct and thus becomes cheapest source
of power to the generating station.
It is generally a three-winding transformer i.e. one primary and two
separate secondary windings. Primary winding of UAT is equal to the main
generator voltage rating. The secondary windings can have same or different
voltages i.e. generally 11KV and or 6.9KV as per plant layout.
23
24
Chapter 3:
Circuit Breaker:
3.1 Sf6 Circuit Breaker:
In such breakers, sulphur hexafluoride gas (SF6) is used as the arc
quenching medium.
The sulphur hexafluoride gas (SF6) is an electronegative gas and
has a strong tendency to absorb free electrons. The contacts of the breaker
are opened in a high pressure flow of sulphur hexafluoride (SF6) gas and
an arc is struck between them. The gas captures the conducting free
electrons in the arc to form relatively immobile negative ions. This loss of
conducting electrons in the arc quickly builds up enough insulation
strength to extinguish the arc.
The sulphur hexafluoride (SF6) circuit breakers have been found to be
very effective for high power and high voltage service.
Construction of SF6 Circuit Breaker:
A sulphur hexafluoride (SF6) circuit breaker consists of fixed and
moving contacts enclosed in a chamber. The chamber is called arc
interruption chamber which contains the sulphur hexafluoride (SF6) gas.
This chamber is connected to sulphur hexafluoride (SF6) gas reservoir. A
25
valve mechanism is there to permit the gas to the arc interruption
chamber. When the contacts of breaker are opened, the valve mechanism
permits a high pressure sulphur hexafluoride (SF6) gas from the reservoir
to flow towards the arc interruption chamber.
The fixed contact is a hollow cylindrical current carrying contact
fitted with an arc horn. The moving contact is also a hollow cylinder with
rectangular holes in the sides. The holes permit the sulphur hexafluoride
gas (SF6) gas to let out through them after flowing along and across the
arc. The tips of fixed contact, moving contact and arcing horn are coated
with copper-tungsten arc resistant material. Since sulphur hexafluoride
gas (SF6) gas is costly, it is reconditioned and reclaimed using suitable
auxiliary system after each operation of breaker.
Working of SF6 CB:
In the closed position of the breaker, the contacts remain
surrounded by sulphur hexafluoride gas (SF6) gas at a pressure of about
2.8 kg/cm2. When the breaker operates, the moving contact is pulled
apart and an arc is struck between the contacts. The movement of the
moving contact is synchronized with the opening of a valve which
permits sulphur hexafluoride gas (SF6) gas at 14 kg/cm2 pressure from
the reservoir to the arc interruption chamber.
The high pressure flow of sulphur hexafluoride gas (SF6) rapidly absorbs
the free electrons in the arc path to form immobile negative ions which
26
are ineffective as charge carriers. The result is that the medium between
the contacts quickly builds up high dielectric strength and causes the
extinction of the arc. After the breaker operation (i.e. after arc extinction),
the valve is closed by the action of a set of springs.
Advantages of SF6:
Due, to the superior arc quenching properties of sulphur
hexafluoride gas (SF6) gas, the sulphur hexafluoride gas (SF6) circuit
breakers have many advantages over oil or air circuit breakers. Some of
them are listed below Due to the superior arc quenching property of
sulphur hexafluoride gas (SF6), such circuit breakers have very short
arcing time.
Since the dielectric strength of sulphur hexafluoride (SF6) gas is 2
to 3 times that operation due unlike of air, such breakers can interrupt
much larger currents.
The sulphur hexafluoride gas (SF6) circuit breaker gives noiseless
operation due its closed gas circuit and no exhaust to atmosphere unlike
the air blast circuit breaker.
27
Chapter 4:
Bus Coupler
4.1 Bus Coupler:
Bus coupler is a device which is used to couple one bus to the other
without any interruption in power supply and without creating hazardous arcs.
Bus coupler is a breaker used to couple two bus-bars in order to perform
maintenance on other circuit breakers associated with that bus-bar.
It is achieved with the help of a circuit breaker and isolators.
28
29
Chapter 5:
11kv incoming and outgoing Panels
5.1 11kv incoming panel:
Specifications:
11KV Incoming Panel for 20/26MVA power transformer with draw out type
vacuumed circuit breaker, 2500A, 25KA, BIL 95KV, One minute power
frequency withstand voltage 36KV, C.T. Ratio 1600:800/5/5A for metering and
protection purpose having class 0.5 and 5P20 respectively, C.T. Ratio
1600:800/5A having protection class 5P20, P.T. 11000/110V AC, complete with
over current and earth fault relay CDG61, Back up earth fault relay CDG21, DC
supervision relay along with DC healthy lamp, 3 phase 4 wire energy meter for
energy metering, moving iron type ampere meter, moving iron type power
factor meter, Moving iron type volt meter with selector switch, On Off push
button and indication lamps, DP and TP control MCB for AC & DC auxiliary
voltage controls, Trip coil 110 V DC, Closing coil 110 V DC, Anti pumping
feature, Spring charging motor 220 V AC, insulators and 99.9% pure tine coated
copper bus bar arrangement covered with heat shrinkable tubing, Cable
termination pads, Earthing ball arrangement for earthing kit, Explosion vents
and Protection class IP3X
30
Nameplate:
31
5.2 11kv outgoing panel:
Specifications:
11KV Outgoing Panel with draw out type vacuumed circuit
breaker, 630A, 25KA, BIL 95KV, One minute power frequency withstand
voltage 36KV, C.T. Ratio 400:200/5/5A, complete with over current and earth
fault relay CDG61, DC supervision relay along with DC healthy lamp, 3 phase 4
wire energy meter for energy metering, moving iron type ampere meter, moving
iron type power factor meter, On Off push button and indication lamps, DP and
TP control MCB for AC & DC auxiliary voltage controls, Trip coil 110 V DC,
Closing coil 110 V DC, Anti pumping feature, Spring charging motor 220 V
AC, insulators and 99.9% pure tine coated copper bus bar arrangement covered
with heat shrinkable insulation tubing, Cable termination pads, Earthing ball
arrangement for earthing kit, explosion vents and Protection class IP3X.
32
Nameplate:
33
Chapter 6
Batteries and Batteries Charger
6.1 Station Batteries System
The purpose of station batteries system is to provide safe and liable
power supply to all primary functions. The system is almost independent of all
other power supply and ensures reliable execution of control functions.
Dc batteries (110V) are installed in grid for protection, emergency
power, alarm and indications.
These batteries have their own battery charger. Under normal
conditions, dc supplies are obtaining through AC to DC rectifier but in case of
failure of AC supplies; DC are used to run the system.
34
Battery Nameplate:
35
Battery Charger Nameplate:
36
Chapter 7:
Electrical Function Numbers
7.1 Introduction:
In the design of electrical power systems, the ANSI standard
device numbers (ANSI /IEEE Standard C37.2 Standard for Electrical Power
System Device Function Numbers, Acronyms, and Contact Designations)
identifies the features of a protective device such as a relay or circuit breaker.
These types of devices protect electrical systems and components from damage
when an unwanted event occurs, such as an electrical fault. Device numbers are
used to identify the functions of devices shown on a schematic diagram.
Function descriptions are given in the standard.
One physical device may correspond to one function number, for
example "29 Isolating Switch", or a single physical device may have many
function numbers associated with it, such as a numerical protective relay. Suffix
and prefix letters may be added to further specify the purpose and function of a
device.
ANSI/IEEE C37.2-2008 is one of a continuing series of revisions
of the standard, which originated in 1928.
7.2 List of device numbers and acronyms:
2 โ€“ Time delay Starting or Closing Relay
3 โ€“ Checking or Interlocking Relay
4 โ€“ Master Contactor
5 โ€“ Stopping
6 โ€“ Starting Circuit Breaker
7 โ€“ Rate of Change Relay
8 โ€“ Control Power Disconnecting Device
9 โ€“ Reversing Device
10 โ€“ Unit Sequence Switch
11 โ€“ Multi-function Device
12 โ€“ Overspeed Device
13 โ€“ Synchronous-speed Device
14 โ€“ Underspeed Device
15 โ€“ Speed โ€“ or Frequency, Matching Device
16 โ€“ Data Communications Device
17 โ€“ Shunting or Discharge Switch
18 โ€“ Accelerating or Decelerating Device
19 โ€“ Starting to Running Transition Contractor
20 โ€“ Electrically Operated Valve
37
21 โ€“ Distance Relay
22 โ€“ Equalizer Circuit Breaker
23 โ€“ Temperature Control Device
24 โ€“ Volts Per Hertz Relay
25 โ€“ Synchronizing or Synchronize-Check Device
26 โ€“ Apparatus Thermal Device
27 โ€“ Undervoltage Relay
27s - DC under voltage Relay
28 โ€“ Flame detector
29 โ€“ Isolating Contactor or Switch
30 โ€“ Annunciator Relay
31 โ€“ Separate Excitation
32 โ€“ Directional Power Relay or Reverse Power Relay
33 โ€“ Position Switch
34 โ€“ Master Sequence Device
35 โ€“ Brush-Operating or Slip-Ring Short-Circuiting Device
36 โ€“ Polarity or Polarizing Voltage Devices
37 โ€“ Undercurrent or Underpower Relay
38 โ€“ Bearing Protective Device
39 โ€“ Mechanical Condition Monitor
40 โ€“ Field (over/under excitation) Relay
41 โ€“ Field Circuit Breaker
42 โ€“ Running Circuit Breaker
43 โ€“ Manual Transfer or Selector Device
44 โ€“ Unit Sequence Starting Relay
45 โ€“ DC over voltage Relay
46 โ€“ Reverse-phase or Phase-Balance Current Relay
47 โ€“ Phase-Sequence or Phase-Balance Voltage Relay
48 โ€“ Incomplete Sequence Relay
49 โ€“ Machine or Transformer, Thermal Relay-OLR
50 โ€“ Instantaneous Overcurrent Relay
50G - Instantaneous Earth Over Current Relay (Neutral CT Method)
50N - Instantaneous Earth Over Current Relay (Residual Method)
50BF - Breaker failure
51 โ€“ AC Inverse Time Overcurrent Relay
51LR - AC Invers Time overcurrent (locked Roter) protection Relay
51G - AC Inverse Time Earth Overcurrent Relay (Neutral CT Method)
51N - AC Inverse Time Earth Overcurrent Relay (Residual Method)
52 โ€“ AC Circuit Breaker
52a - AC Circuit Breaker Position (Contact Open when Breaker Open)
52b - AC Circuit Breaker Position (Contact Closed when Breaker Open)
53 โ€“ Exciter or DC Generator Relay
54 โ€“ Turning Gear Engaging Device
55 โ€“ Power Factor Relay
56 โ€“ Field Application Relay
57 โ€“ Short-Circuiting or Grounding Device
58 โ€“ Rectification Failure Relay
59 โ€“ Overvoltage Relay
60 โ€“ Voltage or Current Balance Relay.
61 โ€“ Density Switch or Sensor
62 โ€“ Time-Delay Stopping or Opening Relay
63 โ€“ Pressure Switch
64 โ€“ Ground Detector Relay
64R - Restricted earth fault
38
64S - Stator earth fault
65 โ€“ Governor
66 โ€“ Notching or Jogging Device
67 โ€“ AC Directional Overcurrent Relay
67N- Directional Earth Fault relay
68 โ€“ Blocking Relay
69 โ€“ Permissive Control Device
70 โ€“ Rheostat
71 โ€“ Liquid Level Switch
72 โ€“ DC Circuit Breaker
73 โ€“ Load-Resistor Contactor
74 โ€“ Alarm Relay
75 โ€“ Position Changing Mechanism
76 โ€“ DC Overcurrent Relay
77 โ€“ Telemetering Device
78 โ€“ Phase-Angle Measuring Relay or "Out-of-Step" Relay
79 โ€“ AC Reclosing Relay (Auto Reclosing)
80 โ€“ Flow Switch
81 โ€“ Frequency Relay
82 โ€“ DC Reclosing Relay
83 โ€“ Automatic Selective Control or Transfer Relay
84 โ€“ Operating Mechanism
85 โ€“ Communications,Carrier or Pilot-Wire Relay
86 โ€“ Lockout Relay/Master Trip
87 โ€“ Differential Protective Relay
88 โ€“ Auxiliary Motor or Motor Generator
89 โ€“ Line Switch
90 โ€“ Regulating Device
91 โ€“ Voltage Directional Relay
92 โ€“ Voltage and Power Directional Relay
93 โ€“ Field Changing Contactor
94 โ€“ Tripping or Trip-Free Relay( trip circuit supervision Relay)
95 โ€“ For specific applications where other numbers are not suitable
96 โ€“ Busbar Trip Lockout relay
97 โ€“ For specific applications where other numbers are not suitable
98 โ€“ For specific applications where other numbers are not suitable
99 โ€“ For specific applications where other numbers are not suitable
150 โ€“ Earth Fault Indicator
AFD โ€“ Arc Flash Detector
CLK โ€“ Clock or Timing Source
DDR โ€“ Dynamic Disturbance Recorder
DFR โ€“ Digital Fault Recorder
DME โ€“ Disturbance Monitor Equipment
HIZ โ€“ High Impedance Fault Detector
HMI โ€“ Human Machine Interface
HST โ€“ Historian
LGC โ€“ Scheme Logic
MET โ€“ Substation Metering
PDC โ€“ Phasor Data Concentrator
PMU โ€“ Phasor Measurement Unit
PQM โ€“ Power Quality Monitor
RIO โ€“ Remote Input/Output Device
RTU โ€“ Remote Terminal Unit/Data Concentrator
SER โ€“ Sequence of Events Recorder
39
7.3 Suffixes and prefixes:
A suffix letter or number may be used with the device
number; for example, suffix N is used if the device is connected to a
Neutral wire (example: 59N in a relay is used for protection against
Neutral Displacement); and suffixes X, Y, Z are used for auxiliary
devices. Similarly, the "G" suffix can denote a "ground"; hence a
"51G" is a time overcurrent ground relay. The "G" suffix can also
mean "generator", hence an "87G" is a Generator Differential
Protective Relay while an "87T" is a Transformer Differential
Protective Relay. "F" can denote "field" on a generator or "fuse", as in
the protective fuse for a pickup transformer. Suffix numbers are used
to distinguish multiple "same" devices in the same equipment such as
51-1, 51โ€“2. Device numbers may be combined if the device provides
multiple functions, such as the instantaneous/time-delay AC over
current relay denoted as 50/51. For device 16, the suffix letters further
define the device: the first suffix letter is 'S' for serial or 'E' for
Ethernet. The subsequent letters are: 'C' security processing function
(e.g. VPN, encryption), 'F' firewall or message filter, 'M' network
managed function, 'R' rotor, and โ€˜Sโ€™ switch and 'T' telephone
component. Thus a managed Ethernet switch would be 16ESM.
40

More Related Content

What's hot

NTDC 220kV Transmission gird station Internship report
NTDC 220kV Transmission gird station Internship reportNTDC 220kV Transmission gird station Internship report
NTDC 220kV Transmission gird station Internship reportAneel-k Suthar
ย 
132 kv sub-station, power transmission
132 kv sub-station, power transmission132 kv sub-station, power transmission
132 kv sub-station, power transmissionprasantakcs
ย 
220 kv G.S.S (report)
220 kv G.S.S (report)220 kv G.S.S (report)
220 kv G.S.S (report)srijan tripathi
ย 
Qasim Pur colony Grid Station Multan
Qasim Pur colony Grid Station MultanQasim Pur colony Grid Station Multan
Qasim Pur colony Grid Station MultanBilal Mayo
ย 
220 kV GSS Mansarovar Jaipur (RVPNL) Training Report SM54
220 kV GSS Mansarovar Jaipur (RVPNL) Training Report SM54220 kV GSS Mansarovar Jaipur (RVPNL) Training Report SM54
220 kV GSS Mansarovar Jaipur (RVPNL) Training Report SM54Subhash Mahla
ย 
ELECTRIC SUB-STATION IN BRIEF
ELECTRIC SUB-STATION IN BRIEFELECTRIC SUB-STATION IN BRIEF
ELECTRIC SUB-STATION IN BRIEFjang041
ย 
Electrical 132kv substation project .. shakir
Electrical 132kv substation project .. shakirElectrical 132kv substation project .. shakir
Electrical 132kv substation project .. shakirSheikh Shakir
ย 
industrial training on 132 kv substation
industrial training on 132 kv substationindustrial training on 132 kv substation
industrial training on 132 kv substationpk130992
ย 
132 k v-substation-training-for-students
132 k v-substation-training-for-students132 k v-substation-training-for-students
132 k v-substation-training-for-studentsSanjay Kumar Sharma
ย 
A 220kV Substation
A 220kV SubstationA 220kV Substation
A 220kV SubstationIshank Ranjan
ย 
132 kv gss sitapura jaipur by mirza
132 kv gss  sitapura jaipur by mirza132 kv gss  sitapura jaipur by mirza
132 kv gss sitapura jaipur by mirzaMIRZA SARMAD BAIG
ย 
66 kv substation
66 kv substation66 kv substation
66 kv substationlovish virmani
ย 
sub-station training report
sub-station training reportsub-station training report
sub-station training reportsitesh95074
ย 
33/11 kV substation (u.p.p.c.l.)
33/11 kV substation (u.p.p.c.l.)33/11 kV substation (u.p.p.c.l.)
33/11 kV substation (u.p.p.c.l.)Prateek Agarwal
ย 
substation 220 kv
substation 220 kv substation 220 kv
substation 220 kv student
ย 
Presentation on KESCO sub-station, kanpur
Presentation on KESCO sub-station, kanpurPresentation on KESCO sub-station, kanpur
Presentation on KESCO sub-station, kanpurShubham Sachan
ย 
Summer Training presentation on 132/33 KV sub-station Minto park, Allahabad
Summer Training presentation on 132/33 KV sub-station Minto park, AllahabadSummer Training presentation on 132/33 KV sub-station Minto park, Allahabad
Summer Training presentation on 132/33 KV sub-station Minto park, AllahabadSudhir Cement Industries Pvt. Ltd. Meerut
ย 
Design T&D of city
Design T&D of cityDesign T&D of city
Design T&D of cityGaurav Singh
ย 
Engineering Final Year Project Report on "Electrical Safety and Protection of...
Engineering Final Year Project Report on "Electrical Safety and Protection of...Engineering Final Year Project Report on "Electrical Safety and Protection of...
Engineering Final Year Project Report on "Electrical Safety and Protection of...Pratap Bhunia
ย 

What's hot (20)

NTDC 220kV Transmission gird station Internship report
NTDC 220kV Transmission gird station Internship reportNTDC 220kV Transmission gird station Internship report
NTDC 220kV Transmission gird station Internship report
ย 
132 kv sub-station, power transmission
132 kv sub-station, power transmission132 kv sub-station, power transmission
132 kv sub-station, power transmission
ย 
220 kv G.S.S (report)
220 kv G.S.S (report)220 kv G.S.S (report)
220 kv G.S.S (report)
ย 
Qasim Pur colony Grid Station Multan
Qasim Pur colony Grid Station MultanQasim Pur colony Grid Station Multan
Qasim Pur colony Grid Station Multan
ย 
220 kV GSS Mansarovar Jaipur (RVPNL) Training Report SM54
220 kV GSS Mansarovar Jaipur (RVPNL) Training Report SM54220 kV GSS Mansarovar Jaipur (RVPNL) Training Report SM54
220 kV GSS Mansarovar Jaipur (RVPNL) Training Report SM54
ย 
ELECTRIC SUB-STATION IN BRIEF
ELECTRIC SUB-STATION IN BRIEFELECTRIC SUB-STATION IN BRIEF
ELECTRIC SUB-STATION IN BRIEF
ย 
Electrical 132kv substation project .. shakir
Electrical 132kv substation project .. shakirElectrical 132kv substation project .. shakir
Electrical 132kv substation project .. shakir
ย 
industrial training on 132 kv substation
industrial training on 132 kv substationindustrial training on 132 kv substation
industrial training on 132 kv substation
ย 
132 k v-substation-training-for-students
132 k v-substation-training-for-students132 k v-substation-training-for-students
132 k v-substation-training-for-students
ย 
A 220kV Substation
A 220kV SubstationA 220kV Substation
A 220kV Substation
ย 
132 kv gss sitapura jaipur by mirza
132 kv gss  sitapura jaipur by mirza132 kv gss  sitapura jaipur by mirza
132 kv gss sitapura jaipur by mirza
ย 
66 kv substation
66 kv substation66 kv substation
66 kv substation
ย 
sub-station training report
sub-station training reportsub-station training report
sub-station training report
ย 
33/11 kV substation (u.p.p.c.l.)
33/11 kV substation (u.p.p.c.l.)33/11 kV substation (u.p.p.c.l.)
33/11 kV substation (u.p.p.c.l.)
ย 
substation 220 kv
substation 220 kv substation 220 kv
substation 220 kv
ย 
132kv G.S.S. Jalore
132kv G.S.S. Jalore132kv G.S.S. Jalore
132kv G.S.S. Jalore
ย 
Presentation on KESCO sub-station, kanpur
Presentation on KESCO sub-station, kanpurPresentation on KESCO sub-station, kanpur
Presentation on KESCO sub-station, kanpur
ย 
Summer Training presentation on 132/33 KV sub-station Minto park, Allahabad
Summer Training presentation on 132/33 KV sub-station Minto park, AllahabadSummer Training presentation on 132/33 KV sub-station Minto park, Allahabad
Summer Training presentation on 132/33 KV sub-station Minto park, Allahabad
ย 
Design T&D of city
Design T&D of cityDesign T&D of city
Design T&D of city
ย 
Engineering Final Year Project Report on "Electrical Safety and Protection of...
Engineering Final Year Project Report on "Electrical Safety and Protection of...Engineering Final Year Project Report on "Electrical Safety and Protection of...
Engineering Final Year Project Report on "Electrical Safety and Protection of...
ย 

Viewers also liked

Solicita ao exmo sr prefeito municipal a realizaรงรฃo de obras de reforma e man...
Solicita ao exmo sr prefeito municipal a realizaรงรฃo de obras de reforma e man...Solicita ao exmo sr prefeito municipal a realizaรงรฃo de obras de reforma e man...
Solicita ao exmo sr prefeito municipal a realizaรงรฃo de obras de reforma e man...drtaylorjr
ย 
12-19-14 CLE for South (P Garrett)
12-19-14 CLE for South (P Garrett)12-19-14 CLE for South (P Garrett)
12-19-14 CLE for South (P Garrett)Patrick Garrett
ย 
ivan Lumala ctodx
ivan Lumala ctodxivan Lumala ctodx
ivan Lumala ctodxIvan Lumala
ย 
Practica de la secun dariaaaaaaaa
Practica de la secun dariaaaaaaaaPractica de la secun dariaaaaaaaa
Practica de la secun dariaaaaaaaatetramegatron
ย 
Information og Kultur: En kรฆrlighedshistorie
Information og Kultur: En kรฆrlighedshistorieInformation og Kultur: En kรฆrlighedshistorie
Information og Kultur: En kรฆrlighedshistorieChristian Lauersen
ย 
Gแบกch bรดng, Gแบกch cแป• ฤ‘แบนp
Gแบกch bรดng, Gแบกch cแป• ฤ‘แบนpGแบกch bรดng, Gแบกch cแป• ฤ‘แบนp
Gแบกch bรดng, Gแบกch cแป• ฤ‘แบนpDiแป…m Hฦฐฦกng
ย 
sami ul haq job cv
sami ul haq job cvsami ul haq job cv
sami ul haq job cvsami ul haq khan
ย 
The Data Labs at Copenhagen University Library: Bringing academia and digital...
The Data Labs at Copenhagen University Library: Bringing academia and digital...The Data Labs at Copenhagen University Library: Bringing academia and digital...
The Data Labs at Copenhagen University Library: Bringing academia and digital...Christian Lauersen
ย 
ุนุฑุจูŠ
ุนุฑุจูŠุนุฑุจูŠ
ุนุฑุจูŠmalakgh
ย 
Suturing techniques & properties of skin /certified fixed orthodontic courses...
Suturing techniques & properties of skin /certified fixed orthodontic courses...Suturing techniques & properties of skin /certified fixed orthodontic courses...
Suturing techniques & properties of skin /certified fixed orthodontic courses...Indian dental academy
ย 
Human Resource Management (WAPDA)
Human Resource Management (WAPDA)Human Resource Management (WAPDA)
Human Resource Management (WAPDA)Hurriya Saeed rana
ย 
Neelum Jhelum Hydropower Internship Report
Neelum Jhelum Hydropower Internship Report Neelum Jhelum Hydropower Internship Report
Neelum Jhelum Hydropower Internship Report muhammad khurram
ย 
Esmolol in Sepsis
Esmolol in SepsisEsmolol in Sepsis
Esmolol in SepsisNIICS
ย 
Wapda internship report
Wapda internship reportWapda internship report
Wapda internship reportMariam Princes
ย 

Viewers also liked (20)

Solicita ao exmo sr prefeito municipal a realizaรงรฃo de obras de reforma e man...
Solicita ao exmo sr prefeito municipal a realizaรงรฃo de obras de reforma e man...Solicita ao exmo sr prefeito municipal a realizaรงรฃo de obras de reforma e man...
Solicita ao exmo sr prefeito municipal a realizaรงรฃo de obras de reforma e man...
ย 
Siete claves para la lectura 3
Siete claves para la lectura 3Siete claves para la lectura 3
Siete claves para la lectura 3
ย 
Vida 1 1
Vida 1 1Vida 1 1
Vida 1 1
ย 
Resultados
ResultadosResultados
Resultados
ย 
12-19-14 CLE for South (P Garrett)
12-19-14 CLE for South (P Garrett)12-19-14 CLE for South (P Garrett)
12-19-14 CLE for South (P Garrett)
ย 
Prebenjamin c
Prebenjamin cPrebenjamin c
Prebenjamin c
ย 
ivan Lumala ctodx
ivan Lumala ctodxivan Lumala ctodx
ivan Lumala ctodx
ย 
Practica de la secun dariaaaaaaaa
Practica de la secun dariaaaaaaaaPractica de la secun dariaaaaaaaa
Practica de la secun dariaaaaaaaa
ย 
Information og Kultur: En kรฆrlighedshistorie
Information og Kultur: En kรฆrlighedshistorieInformation og Kultur: En kรฆrlighedshistorie
Information og Kultur: En kรฆrlighedshistorie
ย 
Gแบกch bรดng, Gแบกch cแป• ฤ‘แบนp
Gแบกch bรดng, Gแบกch cแป• ฤ‘แบนpGแบกch bรดng, Gแบกch cแป• ฤ‘แบนp
Gแบกch bรดng, Gแบกch cแป• ฤ‘แบนp
ย 
sami ul haq job cv
sami ul haq job cvsami ul haq job cv
sami ul haq job cv
ย 
The Data Labs at Copenhagen University Library: Bringing academia and digital...
The Data Labs at Copenhagen University Library: Bringing academia and digital...The Data Labs at Copenhagen University Library: Bringing academia and digital...
The Data Labs at Copenhagen University Library: Bringing academia and digital...
ย 
Internshio report-on-pesco
Internshio report-on-pescoInternshio report-on-pesco
Internshio report-on-pesco
ย 
ุนุฑุจูŠ
ุนุฑุจูŠุนุฑุจูŠ
ุนุฑุจูŠ
ย 
Suturing techniques & properties of skin /certified fixed orthodontic courses...
Suturing techniques & properties of skin /certified fixed orthodontic courses...Suturing techniques & properties of skin /certified fixed orthodontic courses...
Suturing techniques & properties of skin /certified fixed orthodontic courses...
ย 
Human Resource Management (WAPDA)
Human Resource Management (WAPDA)Human Resource Management (WAPDA)
Human Resource Management (WAPDA)
ย 
Neelum Jhelum Hydropower Internship Report
Neelum Jhelum Hydropower Internship Report Neelum Jhelum Hydropower Internship Report
Neelum Jhelum Hydropower Internship Report
ย 
Esmolol in Sepsis
Esmolol in SepsisEsmolol in Sepsis
Esmolol in Sepsis
ย 
Wapda house
Wapda houseWapda house
Wapda house
ย 
Wapda internship report
Wapda internship reportWapda internship report
Wapda internship report
ย 

Similar to Internship Report

Shashikdoc
ShashikdocShashikdoc
ShashikdocShashik132
ย 
Training report-in-a-132-k-v-substation
Training report-in-a-132-k-v-substationTraining report-in-a-132-k-v-substation
Training report-in-a-132-k-v-substationankesh kumar
ย 
Vinay r epo rt
Vinay r epo rtVinay r epo rt
Vinay r epo rtVinay Vashisht
ย 
finalseminar.docx
finalseminar.docxfinalseminar.docx
finalseminar.docxSNEHAKANWAR1
ย 
Industrial training report on dlw varanasi for Main Receiving Substation, Tra...
Industrial training report on dlw varanasi for Main Receiving Substation, Tra...Industrial training report on dlw varanasi for Main Receiving Substation, Tra...
Industrial training report on dlw varanasi for Main Receiving Substation, Tra...Devendra Kumar
ย 
summer internship report on erection, commissioning and pre-comissioning of50...
summer internship report on erection, commissioning and pre-comissioning of50...summer internship report on erection, commissioning and pre-comissioning of50...
summer internship report on erection, commissioning and pre-comissioning of50...Rahul Akinapelli
ย 
INPLANT TRAINING.pptx
INPLANT TRAINING.pptxINPLANT TRAINING.pptx
INPLANT TRAINING.pptxEMovie1
ย 
33-11-kv-substation-training-report (1) (1).pdf
33-11-kv-substation-training-report (1) (1).pdf33-11-kv-substation-training-report (1) (1).pdf
33-11-kv-substation-training-report (1) (1).pdfSagarRana91
ย 
Training at 132 kv substation
Training at 132 kv substation Training at 132 kv substation
Training at 132 kv substation Tejveer Choudhary
ย 
Trainingreport 132 KV
Trainingreport 132 KVTrainingreport 132 KV
Trainingreport 132 KVAbrar Ahamed
ย 
DLW Varanasi Training report
DLW Varanasi Training reportDLW Varanasi Training report
DLW Varanasi Training reportGyanendra Prakash
ย 
Training report of secl , khairha coal mine , sohagpur area for electrical
Training report of secl , khairha coal mine , sohagpur area for electricalTraining report of secl , khairha coal mine , sohagpur area for electrical
Training report of secl , khairha coal mine , sohagpur area for electricalPiyush Dwivedi
ย 
220 kv g.s.s, report
 220 kv g.s.s, report 220 kv g.s.s, report
220 kv g.s.s, reportpanna rayal
ย 
BSES - Maintaince of EHV Equipments
BSES - Maintaince of EHV Equipments BSES - Maintaince of EHV Equipments
BSES - Maintaince of EHV Equipments Anuj Gupta
ย 
Sub-station training REPORT
Sub-station training REPORTSub-station training REPORT
Sub-station training REPORTsitesh95074
ย 

Similar to Internship Report (20)

Shashikdoc
ShashikdocShashikdoc
Shashikdoc
ย 
Training report-in-a-132-k-v-substation
Training report-in-a-132-k-v-substationTraining report-in-a-132-k-v-substation
Training report-in-a-132-k-v-substation
ย 
Vinay r epo rt
Vinay r epo rtVinay r epo rt
Vinay r epo rt
ย 
finalseminar.docx
finalseminar.docxfinalseminar.docx
finalseminar.docx
ย 
Industrial training report on dlw varanasi for Main Receiving Substation, Tra...
Industrial training report on dlw varanasi for Main Receiving Substation, Tra...Industrial training report on dlw varanasi for Main Receiving Substation, Tra...
Industrial training report on dlw varanasi for Main Receiving Substation, Tra...
ย 
summer internship report on erection, commissioning and pre-comissioning of50...
summer internship report on erection, commissioning and pre-comissioning of50...summer internship report on erection, commissioning and pre-comissioning of50...
summer internship report on erection, commissioning and pre-comissioning of50...
ย 
INPLANT TRAINING.pptx
INPLANT TRAINING.pptxINPLANT TRAINING.pptx
INPLANT TRAINING.pptx
ย 
33-11-kv-substation-training-report (1) (1).pdf
33-11-kv-substation-training-report (1) (1).pdf33-11-kv-substation-training-report (1) (1).pdf
33-11-kv-substation-training-report (1) (1).pdf
ย 
Training at 132 kv substation
Training at 132 kv substation Training at 132 kv substation
Training at 132 kv substation
ย 
Indian Railway
Indian Railway Indian Railway
Indian Railway
ย 
33/11 KV SUBSTATION
33/11 KV SUBSTATION33/11 KV SUBSTATION
33/11 KV SUBSTATION
ย 
33 kv substation vt report
33 kv substation vt report33 kv substation vt report
33 kv substation vt report
ย 
Trainingreport 132 KV
Trainingreport 132 KVTrainingreport 132 KV
Trainingreport 132 KV
ย 
DLW Varanasi Training report
DLW Varanasi Training reportDLW Varanasi Training report
DLW Varanasi Training report
ย 
Training report of secl , khairha coal mine , sohagpur area for electrical
Training report of secl , khairha coal mine , sohagpur area for electricalTraining report of secl , khairha coal mine , sohagpur area for electrical
Training report of secl , khairha coal mine , sohagpur area for electrical
ย 
220 kv g.s.s, report
 220 kv g.s.s, report 220 kv g.s.s, report
220 kv g.s.s, report
ย 
BSES - Maintaince of EHV Equipments
BSES - Maintaince of EHV Equipments BSES - Maintaince of EHV Equipments
BSES - Maintaince of EHV Equipments
ย 
ppt on gss
ppt on gssppt on gss
ppt on gss
ย 
ppt on gss
ppt on gssppt on gss
ppt on gss
ย 
Sub-station training REPORT
Sub-station training REPORTSub-station training REPORT
Sub-station training REPORT
ย 

Recently uploaded

Industrial Safety Unit-IV workplace health and safety.ppt
Industrial Safety Unit-IV workplace health and safety.pptIndustrial Safety Unit-IV workplace health and safety.ppt
Industrial Safety Unit-IV workplace health and safety.pptNarmatha D
ย 
Virtual memory management in Operating System
Virtual memory management in Operating SystemVirtual memory management in Operating System
Virtual memory management in Operating SystemRashmi Bhat
ย 
Transport layer issues and challenges - Guide
Transport layer issues and challenges - GuideTransport layer issues and challenges - Guide
Transport layer issues and challenges - GuideGOPINATHS437943
ย 
Arduino_CSE ece ppt for working and principal of arduino.ppt
Arduino_CSE ece ppt for working and principal of arduino.pptArduino_CSE ece ppt for working and principal of arduino.ppt
Arduino_CSE ece ppt for working and principal of arduino.pptSAURABHKUMAR892774
ย 
๐Ÿ”9953056974๐Ÿ”!!-YOUNG call girls in Rajendra Nagar Escort rvice Shot 2000 nigh...
๐Ÿ”9953056974๐Ÿ”!!-YOUNG call girls in Rajendra Nagar Escort rvice Shot 2000 nigh...๐Ÿ”9953056974๐Ÿ”!!-YOUNG call girls in Rajendra Nagar Escort rvice Shot 2000 nigh...
๐Ÿ”9953056974๐Ÿ”!!-YOUNG call girls in Rajendra Nagar Escort rvice Shot 2000 nigh...9953056974 Low Rate Call Girls In Saket, Delhi NCR
ย 
POWER SYSTEMS-1 Complete notes examples
POWER SYSTEMS-1 Complete notes  examplesPOWER SYSTEMS-1 Complete notes  examples
POWER SYSTEMS-1 Complete notes examplesDr. Gudipudi Nageswara Rao
ย 
CCS355 Neural Networks & Deep Learning Unit 1 PDF notes with Question bank .pdf
CCS355 Neural Networks & Deep Learning Unit 1 PDF notes with Question bank .pdfCCS355 Neural Networks & Deep Learning Unit 1 PDF notes with Question bank .pdf
CCS355 Neural Networks & Deep Learning Unit 1 PDF notes with Question bank .pdfAsst.prof M.Gokilavani
ย 
home automation using Arduino by Aditya Prasad
home automation using Arduino by Aditya Prasadhome automation using Arduino by Aditya Prasad
home automation using Arduino by Aditya Prasadaditya806802
ย 
Call Girls Narol 7397865700 Independent Call Girls
Call Girls Narol 7397865700 Independent Call GirlsCall Girls Narol 7397865700 Independent Call Girls
Call Girls Narol 7397865700 Independent Call Girlsssuser7cb4ff
ย 
Unit7-DC_Motors nkkjnsdkfnfcdfknfdgfggfg
Unit7-DC_Motors nkkjnsdkfnfcdfknfdgfggfgUnit7-DC_Motors nkkjnsdkfnfcdfknfdgfggfg
Unit7-DC_Motors nkkjnsdkfnfcdfknfdgfggfgsaravananr517913
ย 
Why does (not) Kafka need fsync: Eliminating tail latency spikes caused by fsync
Why does (not) Kafka need fsync: Eliminating tail latency spikes caused by fsyncWhy does (not) Kafka need fsync: Eliminating tail latency spikes caused by fsync
Why does (not) Kafka need fsync: Eliminating tail latency spikes caused by fsyncssuser2ae721
ย 
Correctly Loading Incremental Data at Scale
Correctly Loading Incremental Data at ScaleCorrectly Loading Incremental Data at Scale
Correctly Loading Incremental Data at ScaleAlluxio, Inc.
ย 
Risk Assessment For Installation of Drainage Pipes.pdf
Risk Assessment For Installation of Drainage Pipes.pdfRisk Assessment For Installation of Drainage Pipes.pdf
Risk Assessment For Installation of Drainage Pipes.pdfROCENODodongVILLACER
ย 
TechTACยฎ CFD Report Summary: A Comparison of Two Types of Tubing Anchor Catchers
TechTACยฎ CFD Report Summary: A Comparison of Two Types of Tubing Anchor CatchersTechTACยฎ CFD Report Summary: A Comparison of Two Types of Tubing Anchor Catchers
TechTACยฎ CFD Report Summary: A Comparison of Two Types of Tubing Anchor Catcherssdickerson1
ย 
Work Experience-Dalton Park.pptxfvvvvvvv
Work Experience-Dalton Park.pptxfvvvvvvvWork Experience-Dalton Park.pptxfvvvvvvv
Work Experience-Dalton Park.pptxfvvvvvvvLewisJB
ย 
Mine Environment II Lab_MI10448MI__________.pptx
Mine Environment II Lab_MI10448MI__________.pptxMine Environment II Lab_MI10448MI__________.pptx
Mine Environment II Lab_MI10448MI__________.pptxRomil Mishra
ย 
Main Memory Management in Operating System
Main Memory Management in Operating SystemMain Memory Management in Operating System
Main Memory Management in Operating SystemRashmi Bhat
ย 
Internet of things -Arshdeep Bahga .pptx
Internet of things -Arshdeep Bahga .pptxInternet of things -Arshdeep Bahga .pptx
Internet of things -Arshdeep Bahga .pptxVelmuruganTECE
ย 
System Simulation and Modelling with types and Event Scheduling
System Simulation and Modelling with types and Event SchedulingSystem Simulation and Modelling with types and Event Scheduling
System Simulation and Modelling with types and Event SchedulingBootNeck1
ย 

Recently uploaded (20)

Industrial Safety Unit-IV workplace health and safety.ppt
Industrial Safety Unit-IV workplace health and safety.pptIndustrial Safety Unit-IV workplace health and safety.ppt
Industrial Safety Unit-IV workplace health and safety.ppt
ย 
Virtual memory management in Operating System
Virtual memory management in Operating SystemVirtual memory management in Operating System
Virtual memory management in Operating System
ย 
Transport layer issues and challenges - Guide
Transport layer issues and challenges - GuideTransport layer issues and challenges - Guide
Transport layer issues and challenges - Guide
ย 
Arduino_CSE ece ppt for working and principal of arduino.ppt
Arduino_CSE ece ppt for working and principal of arduino.pptArduino_CSE ece ppt for working and principal of arduino.ppt
Arduino_CSE ece ppt for working and principal of arduino.ppt
ย 
๐Ÿ”9953056974๐Ÿ”!!-YOUNG call girls in Rajendra Nagar Escort rvice Shot 2000 nigh...
๐Ÿ”9953056974๐Ÿ”!!-YOUNG call girls in Rajendra Nagar Escort rvice Shot 2000 nigh...๐Ÿ”9953056974๐Ÿ”!!-YOUNG call girls in Rajendra Nagar Escort rvice Shot 2000 nigh...
๐Ÿ”9953056974๐Ÿ”!!-YOUNG call girls in Rajendra Nagar Escort rvice Shot 2000 nigh...
ย 
POWER SYSTEMS-1 Complete notes examples
POWER SYSTEMS-1 Complete notes  examplesPOWER SYSTEMS-1 Complete notes  examples
POWER SYSTEMS-1 Complete notes examples
ย 
CCS355 Neural Networks & Deep Learning Unit 1 PDF notes with Question bank .pdf
CCS355 Neural Networks & Deep Learning Unit 1 PDF notes with Question bank .pdfCCS355 Neural Networks & Deep Learning Unit 1 PDF notes with Question bank .pdf
CCS355 Neural Networks & Deep Learning Unit 1 PDF notes with Question bank .pdf
ย 
home automation using Arduino by Aditya Prasad
home automation using Arduino by Aditya Prasadhome automation using Arduino by Aditya Prasad
home automation using Arduino by Aditya Prasad
ย 
Call Girls Narol 7397865700 Independent Call Girls
Call Girls Narol 7397865700 Independent Call GirlsCall Girls Narol 7397865700 Independent Call Girls
Call Girls Narol 7397865700 Independent Call Girls
ย 
Unit7-DC_Motors nkkjnsdkfnfcdfknfdgfggfg
Unit7-DC_Motors nkkjnsdkfnfcdfknfdgfggfgUnit7-DC_Motors nkkjnsdkfnfcdfknfdgfggfg
Unit7-DC_Motors nkkjnsdkfnfcdfknfdgfggfg
ย 
Why does (not) Kafka need fsync: Eliminating tail latency spikes caused by fsync
Why does (not) Kafka need fsync: Eliminating tail latency spikes caused by fsyncWhy does (not) Kafka need fsync: Eliminating tail latency spikes caused by fsync
Why does (not) Kafka need fsync: Eliminating tail latency spikes caused by fsync
ย 
Correctly Loading Incremental Data at Scale
Correctly Loading Incremental Data at ScaleCorrectly Loading Incremental Data at Scale
Correctly Loading Incremental Data at Scale
ย 
Risk Assessment For Installation of Drainage Pipes.pdf
Risk Assessment For Installation of Drainage Pipes.pdfRisk Assessment For Installation of Drainage Pipes.pdf
Risk Assessment For Installation of Drainage Pipes.pdf
ย 
TechTACยฎ CFD Report Summary: A Comparison of Two Types of Tubing Anchor Catchers
TechTACยฎ CFD Report Summary: A Comparison of Two Types of Tubing Anchor CatchersTechTACยฎ CFD Report Summary: A Comparison of Two Types of Tubing Anchor Catchers
TechTACยฎ CFD Report Summary: A Comparison of Two Types of Tubing Anchor Catchers
ย 
Work Experience-Dalton Park.pptxfvvvvvvv
Work Experience-Dalton Park.pptxfvvvvvvvWork Experience-Dalton Park.pptxfvvvvvvv
Work Experience-Dalton Park.pptxfvvvvvvv
ย 
Mine Environment II Lab_MI10448MI__________.pptx
Mine Environment II Lab_MI10448MI__________.pptxMine Environment II Lab_MI10448MI__________.pptx
Mine Environment II Lab_MI10448MI__________.pptx
ย 
young call girls in Rajiv Chowk๐Ÿ” 9953056974 ๐Ÿ” Delhi escort Service
young call girls in Rajiv Chowk๐Ÿ” 9953056974 ๐Ÿ” Delhi escort Serviceyoung call girls in Rajiv Chowk๐Ÿ” 9953056974 ๐Ÿ” Delhi escort Service
young call girls in Rajiv Chowk๐Ÿ” 9953056974 ๐Ÿ” Delhi escort Service
ย 
Main Memory Management in Operating System
Main Memory Management in Operating SystemMain Memory Management in Operating System
Main Memory Management in Operating System
ย 
Internet of things -Arshdeep Bahga .pptx
Internet of things -Arshdeep Bahga .pptxInternet of things -Arshdeep Bahga .pptx
Internet of things -Arshdeep Bahga .pptx
ย 
System Simulation and Modelling with types and Event Scheduling
System Simulation and Modelling with types and Event SchedulingSystem Simulation and Modelling with types and Event Scheduling
System Simulation and Modelling with types and Event Scheduling
ย 

Internship Report

  • 1. Internship Training Report 132kv Grid Substation Kamalabad, P&I IESCO by Muhammad Usman Rafiq F-4068 A Report submitted to the Department of P&I, IESCO Islamabad in partial fulfillment of the requirements for the internship of one month for BACHELOR OF SCIENCE IN ELECTRICAL ENGINEERING P&I, IESCO Islamabad, 46000 Pakistan <August, 2016>
  • 2. ii Copyright ยฉ 2014 by APCOMS All rights reserved. Reproduction in whole or in part in any form requires the prior written permission of Muhammad Usman Rafiq or designated representative.
  • 3. DEDICATION Thanks to almighty Allah, who makes me, grows me and produces such abilities in me so I become able to produce such report. I want to dedicate โ€œMy Little Workโ€ to my parents and teachers. Parents and teachers have a great role in my life. Both the personalities exert a lot of efforts on me which make me eligible for making this report.
  • 4. C E R T I F I C A T E O F A P P R O V A L It is certified that the work of report titled โ€œ132K Internship Training Report 132kv Grid Substation Kamalabad, P&I IESCOโ€ is carried out by Muhammad Usman Rafiq, Roll. No F-4068, under the supervision of IESCO, at Islamabad and Rawalpindi. It is fully adequate, in scope and in quality, as a report for the internship of one month. Supervisor: ------------------------
  • 5. ACKNOWLEDGMENT IESCO has been the ideal training institute. Officials deputed are highly trained; their sage advices, insightful criticisms, and patient encouragement aided this report in innumerable ways. I would also like to thank trainers which steadfast support of this report was greatly needed and deeply appreciated.
  • 6. DECLARATION We hereby declare that this project, neither as a whole nor as a part thereof has been copied from any source. It is further declared that we have developed this report entirely on the basis of our personal efforts under the sincere guidance of IESCO officials. ______________________ Muhammad Usman Rafiq
  • 7. ABSTRACT Now a dayโ€™s everything is depending up on the power. So give the reliable supply to the consumers. In distribution systems one of the major parts is "SUBSTATIONS". An electrical substation is a subsidiary station of an electricity, Generation, Transmission and distribution systems where the voltage is transformed from high to low or reverse using the transformers .Electric power may flow through several substations between generating plant and consumer and may be changed in different voltage levels .the equipment used in substation are Transformer, Lightening arresters, isolator, bus bar, protective devices, Battery charger, earth switches, earth rods. So for of supply the regular maintenance and checking is necessary from that we conclude weather it is suitable or not for the desired operation.
  • 8. TABLE OF CONTENTS Chapter 1 Introduction ....................................................................... 8 1.1 Substation .................................................................... 8 1.2 132Kv single-line grid substation diagram ............................... 9 1.2 Classification of substation ...................................................... 10 1.3 Function of substation ................................................. 11 Chapter 2 Equipment Used in a Sub Station โ€ฆโ€ฆ.................................. 12 2.1 Transformer ...................................................................... 12 Types of transformer 2.1.1 Power Transformer ............................................. 12 2.1.1.1 Parts of transformer 1. Conservative Tank .................................. 14 2. Tape Changer .......................... 15 3. Buchholz Relay .......................... 16 4. Silica Gel .......................... 17 2.1.2 Instrument transformer ........................ 19 2.1.2.1 Current transformer ........................ 19 2.1.2.2 Potential transformer ........................ 20 2.1.2.3 Unit Auxiliary transformer ........................ 21 Chapter 3 Circuit Breaker โ€ฆโ€ฆโ€ฆโ€ฆ......................................................... 24 3.1 S F 6 g a s c i r c u i t b r e a k e r ........................... 24 Chapter 4 Bus Coupler ................................................... 27 4.1 Bus coupler ....................................... 27 Chapter 5
  • 9. 11kv incoming and outgoing Panels ................................................. 29 5.1 11kv incoming Panels .............................................................. 29 5.2 11kv outgoing Panels .............................................................. 31 Chapter 6 Batteries and Batteries Charger ................................................. 32 6.1 Station Batteries System ................................................. 32 Chapter 7 Electrical Function Numbers ............................................. 36 7.1 Introduction ................................................. 36 7.2 List of device numbers and acronyms ........................................ 36 7.3 Suffixes and prefixes ........................................ 39
  • 10. CHAPTER 1 Introduction: The present day electrical power system is a.c i.e. electric power is generated, transmitted and distributed in the form of Alternating current. The electric power is produce at the power station, which are located at favorable places. It is delivered to the consumer through a large network of transmission and distribution. At many place in the line of power system, it may be desirable and necessary to change some characteristic ( e.g. Voltage, ac to dc, frequency p.f. etc.) of electric supply. This is accomplished by suitable apparatus called sub-station for example, generation voltage (11kv or 6.6kv) at the power station is stepped up to high voltage (Say 220kv to 132kv) for transmission of electric power. Similarly near the consumerโ€™s localities, the voltage may have to be stepped down to utilization level. This job is again accomplished by suitable apparatus called sub-stations. 1.1 Substation: An electrical substation is a subsidiary station of an electricity generation, transmission and distribution system where voltage is transformed high to low or the reverse using transformers. Electric power may flow through several substations between generation plant and consumer, and may be changed in voltage in several steps. The main equipment used in substation are transformers lighting arresters, Circuit breakers PLCC, isolators, bus bars, protective relays, Battery 8
  • 11. charger, earth switches, earth rods. . 9
  • 12. 1.2 Classification of substations: Classification of substations based on (1) Service requirements (2) Constructional features 1. According to service requirements: According to service requirements substations are classified into: i. Transformer Substations ii. Switching Substations iii. Power factor correction substations iv. Frequency changer substations v. Converting substations vi. Industrial substations 2. According to construction features: According to constructional features substations are classified as; i. Indoor substations ii. Outdoor substations iii. Underground substations iv. Pole mounted substations 10
  • 13. 1.3 Functions of a Substation: 1 - Supply of required electrical power. 2 - Maximum possible coverage of the supply network. 3 - Maximum security of supply. 4 - Shortest possible fault-duration. 5 - Optimum efficiency of plants and the network. 6 - Supply of electrical power within targeted frequency limits, (49.5 Hz and50.5 Hz). 7 - Supply of electrical power within specified voltage limits. 8 - Supply of electrical energy to the consumers at the lowest cost. 11
  • 14. Chapter 2 Equipment Used in a Sub-Station The equipment required for a transformer Sub-Station depends upon the type of Sub-Station, Service requirement and the degree of protection desired. TIF Sub-Station has the following major equipments. 2.1 Transformers: Transformer is a static machine, which transforms the potential of alternating current at same frequency. It means the transformer transforms the low voltage into high voltage & high voltage to low voltage at same frequency. It works on the principle of static induction principle. When the energy is transformed into a higher voltage, the transformer is called step up transformer but in case of other is known as step down transformer. TYPES OF TRANSFORMERS 2.1.1 Power Transformer: It is used for the transmission purpose at heavy load, high voltage greater than 33 KV & 100% efficiency. It also having a big in size as compare to distribution transformer, it used in generating station and Transmission substation at high insulation level. They can be of two types: Single Phase Transformers and Multi Phase Transformers. 12
  • 15. 13
  • 17. 2.1.1.1 Parts of power transformer: 15
  • 18. i. Conservator Tank: This is a cylindrical tank mounted on supporting structure on the roof the transformer main tank. The main function of conservator tank of transformer is to provide adequate space for expansion of oil inside the transformer. Function of Conservator Tank of a Transformer: When transformer is loaded and when ambient temperature rises, the volume of oil inside transformer increases. A conservator tank of transformer provides adequate space to this expanded transformer oil. It also acts as a reservoir for transformer insulating oil. Construction of Conservator Tank: This is a cylindrical shaped oil container closed from both ends. One large inspection cover is provided on either side of the container to facilitate maintenance and cleaning inside of the conservator. Conservator pipe, i.e. pipe comes from main transformer tank, is projected inside the conservator from bottom portion. Head of the conservator pipe inside the conservator is provided with a cap. This pipe is projected as well as provided with a cap because this design prevents oil sludge and sediment to enter into main tank from conservator. Generally silica gel breather fixing pipe enters into the conservator from top. If it enters from bottom, it should be projected well above the level of oil inside the conservator. This arrangement ensures that oil does not enter the silica gel breather even at highest operating level. 16
  • 19. Working of Conservator Tank: When volume of transformer insulating oil increases due to load and ambient temperature, the vacant space above the oil level inside the conservator is partially occupied by the expanded oil. Consequently, corresponding quantity of air of that space is pushed away through breather. On other hand, when load of transformer decreases, the transformer is switched off and when the ambient temperature decreases, the oil inside the transformer contracts. This causes outside air to enter in the conservator tank of transformer through silica gel breather. ii. Tape Changer: A tap changer is a connection point selection mechanism along a power transformer winding that allows a variable number of turns to be selected in discrete steps. A transformer with a variable turns ratio is produced, enabling stepped voltage regulation of the output. The tap selection may be made via an automatic or manual tap changer mechanism. 17
  • 20. Voltage considerations: If only one tap changer is required, manually operated tap points are usually made on the high voltage (primary) or lower current winding of the transformer to minimize the current handling requirements of the contacts. However, a transformer may include a tap changer on each winding if there are advantages to do so. For example, in power distribution networks, a large step-down transformer may have an off- load tap changer on the primary winding and an on-load automatic tap changer on the secondary winding or windings. The high voltage tap is set to match long term system profile on the high voltage network (typically supply voltage averages) and is rarely changed. The low voltage tap may be requested to change positions multiple times each day, without interrupting the power delivery, to follow loading conditions on the low-voltage (secondary winding) network. To minimize the number of winding taps and thus reduce the physical size of a tap changing transformer, a 'reversing' tap changer winding may be used, which is a portion of the main winding able to be connected in its opposite direction (buck) and thus oppose the voltage. iii. Buchholz Relay: Buchholz relay in transformer is an oil container housed the connecting pipe from main tank to conservator tank. It has mainly two elements. The upper element consists of a float. The float is attached to a hinge in such a way that it can move up and down depending upon the oil level in the Buchholz relay Container. One mercury switch is fixed on the float. The alignment of mercury switch hence depends upon the position of the float. The lower element consists of a baffle plate and mercury switch. This plate is fitted on a hinge just in front of the inlet (main tank side) of Buchholz relay in transformer in such a way that when oil enters in the relay from that inlet in high pressure the alignment of the baffle plate along with the mercury switch attached to it, will change. 18
  • 21. In addition to these main elements a Buchholz relay has gas release pockets on top. The electrical leads from both mercury switches are taken out through a molded terminal block. iv. Silica Gel Breather of Transformer: Whenever electrical power transformer is loaded, the temperature of the transformer insulating oil increases, consequently the volume of the oil is increased. As the volume of the oil is increased, the air above the oil level in conservator will come out. Again at low oil temperature; the volume of the oil is decreased, which causes the volume of the oil to be decreased which again causes air to enter into conservator tank. The natural air always consists of more or less moisture in it and this moisture can be mixed up with oil if it is allowed to enter into the transformer. The air moisture should be resisted during entering of the air into the transformer, because moisture is very harmful for transformer insulation. A silica gel breather is the most commonly used way of filtering air from moisture. Silica gel breather for transformer is connected with conservator tank by means of breathing pipe. 19
  • 22. Construction of Silica Gel Breather: The silica gel breather of transformer is very simple in the aspect of design. It is nothing but a pot of silica gel through which, air passes during breathing of transformer. The silica gel is a very good absorber of moisture. Freshly regenerated gel is very efficient, it may dry down air to a dew point of below โˆ’40ยฐC. A well maintained silica gel breather will generally operate with a dew point of โˆ’35ยฐC as long as a large enough quantity of gel has been used. The picture shows a silica gel breather of transformer. Working Principle of Silica Gel Breather: Silica gel crystal has tremendous capacity of absorbing moisture. When air passes through these crystals in the breather; the moisture of the air is absorbed by them. Therefore, the air reaches to the conservator is quite dry, the dust particles in the air get trapped by the oil in the oil seal cup. The oil in the oil sealing cup acts as barrier between silica gel crystal and air when there is no flow of air through silica gel breather. The color of silica gel crystal is dark blue but, when it absorbs moisture; it becomes pink. When there is sufficient difference between the air inside the conservator and the outside air, the oil level in two components of the oil seal changes until the lower oil level just reaches the rim of the inverted cup, the air then moves from high pressure compartment to the low pressure compartment of the oil 20
  • 23. seal. Both of these happen when the oil acts as core filter and removes the dust from the outside air. 2.1.2 Instrument Transformers: These transformers are used for the measurement purposes at that points where standard voltmeters and ammeters cannot be used. They are of two types: 2.1.2.1 CURRENT TRANSFORMER: A current transformer (CT) is used for measurement of alternating electric currents. When current in a circuit is too high to apply directly to measuring instruments, a current transformer produces a reduced current accurately proportional to the current in the circuit, which can be conveniently connected to measuring and recording instruments. A current transformer isolates the measuring instruments from what may be very high voltage in the monitored circuit. Nameplate: 21
  • 24. 2.1.2.2 POTENTIAL OR VOLTAGE TRANSFORMER: Voltage transformers (VT) (also called potential transformers (PT)) are a parallel connected type of instrument transformer, used for metering and protection in high-voltage circuits or phase shift isolation. They are designed to present negligible load to the supply being measured and to have an accurate voltage ratio to enable accurate metering. A potential transformer may have several secondary windings on the same core as a primary winding, for use in different metering or protection circuits. Nameplate: 22
  • 25. 2.1.2.3 Unit Auxiliary Transformers (UAT) The Unit Auxiliary Transformer is the Power Transformer that provides power to the auxiliary equipment of a power generating station during its normal operation. This transformer is connected directly to the generator out- put by a tap-off of the isolated phase bus duct and thus becomes cheapest source of power to the generating station. It is generally a three-winding transformer i.e. one primary and two separate secondary windings. Primary winding of UAT is equal to the main generator voltage rating. The secondary windings can have same or different voltages i.e. generally 11KV and or 6.9KV as per plant layout. 23
  • 26. 24
  • 27. Chapter 3: Circuit Breaker: 3.1 Sf6 Circuit Breaker: In such breakers, sulphur hexafluoride gas (SF6) is used as the arc quenching medium. The sulphur hexafluoride gas (SF6) is an electronegative gas and has a strong tendency to absorb free electrons. The contacts of the breaker are opened in a high pressure flow of sulphur hexafluoride (SF6) gas and an arc is struck between them. The gas captures the conducting free electrons in the arc to form relatively immobile negative ions. This loss of conducting electrons in the arc quickly builds up enough insulation strength to extinguish the arc. The sulphur hexafluoride (SF6) circuit breakers have been found to be very effective for high power and high voltage service. Construction of SF6 Circuit Breaker: A sulphur hexafluoride (SF6) circuit breaker consists of fixed and moving contacts enclosed in a chamber. The chamber is called arc interruption chamber which contains the sulphur hexafluoride (SF6) gas. This chamber is connected to sulphur hexafluoride (SF6) gas reservoir. A 25
  • 28. valve mechanism is there to permit the gas to the arc interruption chamber. When the contacts of breaker are opened, the valve mechanism permits a high pressure sulphur hexafluoride (SF6) gas from the reservoir to flow towards the arc interruption chamber. The fixed contact is a hollow cylindrical current carrying contact fitted with an arc horn. The moving contact is also a hollow cylinder with rectangular holes in the sides. The holes permit the sulphur hexafluoride gas (SF6) gas to let out through them after flowing along and across the arc. The tips of fixed contact, moving contact and arcing horn are coated with copper-tungsten arc resistant material. Since sulphur hexafluoride gas (SF6) gas is costly, it is reconditioned and reclaimed using suitable auxiliary system after each operation of breaker. Working of SF6 CB: In the closed position of the breaker, the contacts remain surrounded by sulphur hexafluoride gas (SF6) gas at a pressure of about 2.8 kg/cm2. When the breaker operates, the moving contact is pulled apart and an arc is struck between the contacts. The movement of the moving contact is synchronized with the opening of a valve which permits sulphur hexafluoride gas (SF6) gas at 14 kg/cm2 pressure from the reservoir to the arc interruption chamber. The high pressure flow of sulphur hexafluoride gas (SF6) rapidly absorbs the free electrons in the arc path to form immobile negative ions which 26
  • 29. are ineffective as charge carriers. The result is that the medium between the contacts quickly builds up high dielectric strength and causes the extinction of the arc. After the breaker operation (i.e. after arc extinction), the valve is closed by the action of a set of springs. Advantages of SF6: Due, to the superior arc quenching properties of sulphur hexafluoride gas (SF6) gas, the sulphur hexafluoride gas (SF6) circuit breakers have many advantages over oil or air circuit breakers. Some of them are listed below Due to the superior arc quenching property of sulphur hexafluoride gas (SF6), such circuit breakers have very short arcing time. Since the dielectric strength of sulphur hexafluoride (SF6) gas is 2 to 3 times that operation due unlike of air, such breakers can interrupt much larger currents. The sulphur hexafluoride gas (SF6) circuit breaker gives noiseless operation due its closed gas circuit and no exhaust to atmosphere unlike the air blast circuit breaker. 27
  • 30. Chapter 4: Bus Coupler 4.1 Bus Coupler: Bus coupler is a device which is used to couple one bus to the other without any interruption in power supply and without creating hazardous arcs. Bus coupler is a breaker used to couple two bus-bars in order to perform maintenance on other circuit breakers associated with that bus-bar. It is achieved with the help of a circuit breaker and isolators. 28
  • 31. 29
  • 32. Chapter 5: 11kv incoming and outgoing Panels 5.1 11kv incoming panel: Specifications: 11KV Incoming Panel for 20/26MVA power transformer with draw out type vacuumed circuit breaker, 2500A, 25KA, BIL 95KV, One minute power frequency withstand voltage 36KV, C.T. Ratio 1600:800/5/5A for metering and protection purpose having class 0.5 and 5P20 respectively, C.T. Ratio 1600:800/5A having protection class 5P20, P.T. 11000/110V AC, complete with over current and earth fault relay CDG61, Back up earth fault relay CDG21, DC supervision relay along with DC healthy lamp, 3 phase 4 wire energy meter for energy metering, moving iron type ampere meter, moving iron type power factor meter, Moving iron type volt meter with selector switch, On Off push button and indication lamps, DP and TP control MCB for AC & DC auxiliary voltage controls, Trip coil 110 V DC, Closing coil 110 V DC, Anti pumping feature, Spring charging motor 220 V AC, insulators and 99.9% pure tine coated copper bus bar arrangement covered with heat shrinkable tubing, Cable termination pads, Earthing ball arrangement for earthing kit, Explosion vents and Protection class IP3X 30
  • 34. 5.2 11kv outgoing panel: Specifications: 11KV Outgoing Panel with draw out type vacuumed circuit breaker, 630A, 25KA, BIL 95KV, One minute power frequency withstand voltage 36KV, C.T. Ratio 400:200/5/5A, complete with over current and earth fault relay CDG61, DC supervision relay along with DC healthy lamp, 3 phase 4 wire energy meter for energy metering, moving iron type ampere meter, moving iron type power factor meter, On Off push button and indication lamps, DP and TP control MCB for AC & DC auxiliary voltage controls, Trip coil 110 V DC, Closing coil 110 V DC, Anti pumping feature, Spring charging motor 220 V AC, insulators and 99.9% pure tine coated copper bus bar arrangement covered with heat shrinkable insulation tubing, Cable termination pads, Earthing ball arrangement for earthing kit, explosion vents and Protection class IP3X. 32
  • 36. Chapter 6 Batteries and Batteries Charger 6.1 Station Batteries System The purpose of station batteries system is to provide safe and liable power supply to all primary functions. The system is almost independent of all other power supply and ensures reliable execution of control functions. Dc batteries (110V) are installed in grid for protection, emergency power, alarm and indications. These batteries have their own battery charger. Under normal conditions, dc supplies are obtaining through AC to DC rectifier but in case of failure of AC supplies; DC are used to run the system. 34
  • 39. Chapter 7: Electrical Function Numbers 7.1 Introduction: In the design of electrical power systems, the ANSI standard device numbers (ANSI /IEEE Standard C37.2 Standard for Electrical Power System Device Function Numbers, Acronyms, and Contact Designations) identifies the features of a protective device such as a relay or circuit breaker. These types of devices protect electrical systems and components from damage when an unwanted event occurs, such as an electrical fault. Device numbers are used to identify the functions of devices shown on a schematic diagram. Function descriptions are given in the standard. One physical device may correspond to one function number, for example "29 Isolating Switch", or a single physical device may have many function numbers associated with it, such as a numerical protective relay. Suffix and prefix letters may be added to further specify the purpose and function of a device. ANSI/IEEE C37.2-2008 is one of a continuing series of revisions of the standard, which originated in 1928. 7.2 List of device numbers and acronyms: 2 โ€“ Time delay Starting or Closing Relay 3 โ€“ Checking or Interlocking Relay 4 โ€“ Master Contactor 5 โ€“ Stopping 6 โ€“ Starting Circuit Breaker 7 โ€“ Rate of Change Relay 8 โ€“ Control Power Disconnecting Device 9 โ€“ Reversing Device 10 โ€“ Unit Sequence Switch 11 โ€“ Multi-function Device 12 โ€“ Overspeed Device 13 โ€“ Synchronous-speed Device 14 โ€“ Underspeed Device 15 โ€“ Speed โ€“ or Frequency, Matching Device 16 โ€“ Data Communications Device 17 โ€“ Shunting or Discharge Switch 18 โ€“ Accelerating or Decelerating Device 19 โ€“ Starting to Running Transition Contractor 20 โ€“ Electrically Operated Valve 37
  • 40. 21 โ€“ Distance Relay 22 โ€“ Equalizer Circuit Breaker 23 โ€“ Temperature Control Device 24 โ€“ Volts Per Hertz Relay 25 โ€“ Synchronizing or Synchronize-Check Device 26 โ€“ Apparatus Thermal Device 27 โ€“ Undervoltage Relay 27s - DC under voltage Relay 28 โ€“ Flame detector 29 โ€“ Isolating Contactor or Switch 30 โ€“ Annunciator Relay 31 โ€“ Separate Excitation 32 โ€“ Directional Power Relay or Reverse Power Relay 33 โ€“ Position Switch 34 โ€“ Master Sequence Device 35 โ€“ Brush-Operating or Slip-Ring Short-Circuiting Device 36 โ€“ Polarity or Polarizing Voltage Devices 37 โ€“ Undercurrent or Underpower Relay 38 โ€“ Bearing Protective Device 39 โ€“ Mechanical Condition Monitor 40 โ€“ Field (over/under excitation) Relay 41 โ€“ Field Circuit Breaker 42 โ€“ Running Circuit Breaker 43 โ€“ Manual Transfer or Selector Device 44 โ€“ Unit Sequence Starting Relay 45 โ€“ DC over voltage Relay 46 โ€“ Reverse-phase or Phase-Balance Current Relay 47 โ€“ Phase-Sequence or Phase-Balance Voltage Relay 48 โ€“ Incomplete Sequence Relay 49 โ€“ Machine or Transformer, Thermal Relay-OLR 50 โ€“ Instantaneous Overcurrent Relay 50G - Instantaneous Earth Over Current Relay (Neutral CT Method) 50N - Instantaneous Earth Over Current Relay (Residual Method) 50BF - Breaker failure 51 โ€“ AC Inverse Time Overcurrent Relay 51LR - AC Invers Time overcurrent (locked Roter) protection Relay 51G - AC Inverse Time Earth Overcurrent Relay (Neutral CT Method) 51N - AC Inverse Time Earth Overcurrent Relay (Residual Method) 52 โ€“ AC Circuit Breaker 52a - AC Circuit Breaker Position (Contact Open when Breaker Open) 52b - AC Circuit Breaker Position (Contact Closed when Breaker Open) 53 โ€“ Exciter or DC Generator Relay 54 โ€“ Turning Gear Engaging Device 55 โ€“ Power Factor Relay 56 โ€“ Field Application Relay 57 โ€“ Short-Circuiting or Grounding Device 58 โ€“ Rectification Failure Relay 59 โ€“ Overvoltage Relay 60 โ€“ Voltage or Current Balance Relay. 61 โ€“ Density Switch or Sensor 62 โ€“ Time-Delay Stopping or Opening Relay 63 โ€“ Pressure Switch 64 โ€“ Ground Detector Relay 64R - Restricted earth fault 38
  • 41. 64S - Stator earth fault 65 โ€“ Governor 66 โ€“ Notching or Jogging Device 67 โ€“ AC Directional Overcurrent Relay 67N- Directional Earth Fault relay 68 โ€“ Blocking Relay 69 โ€“ Permissive Control Device 70 โ€“ Rheostat 71 โ€“ Liquid Level Switch 72 โ€“ DC Circuit Breaker 73 โ€“ Load-Resistor Contactor 74 โ€“ Alarm Relay 75 โ€“ Position Changing Mechanism 76 โ€“ DC Overcurrent Relay 77 โ€“ Telemetering Device 78 โ€“ Phase-Angle Measuring Relay or "Out-of-Step" Relay 79 โ€“ AC Reclosing Relay (Auto Reclosing) 80 โ€“ Flow Switch 81 โ€“ Frequency Relay 82 โ€“ DC Reclosing Relay 83 โ€“ Automatic Selective Control or Transfer Relay 84 โ€“ Operating Mechanism 85 โ€“ Communications,Carrier or Pilot-Wire Relay 86 โ€“ Lockout Relay/Master Trip 87 โ€“ Differential Protective Relay 88 โ€“ Auxiliary Motor or Motor Generator 89 โ€“ Line Switch 90 โ€“ Regulating Device 91 โ€“ Voltage Directional Relay 92 โ€“ Voltage and Power Directional Relay 93 โ€“ Field Changing Contactor 94 โ€“ Tripping or Trip-Free Relay( trip circuit supervision Relay) 95 โ€“ For specific applications where other numbers are not suitable 96 โ€“ Busbar Trip Lockout relay 97 โ€“ For specific applications where other numbers are not suitable 98 โ€“ For specific applications where other numbers are not suitable 99 โ€“ For specific applications where other numbers are not suitable 150 โ€“ Earth Fault Indicator AFD โ€“ Arc Flash Detector CLK โ€“ Clock or Timing Source DDR โ€“ Dynamic Disturbance Recorder DFR โ€“ Digital Fault Recorder DME โ€“ Disturbance Monitor Equipment HIZ โ€“ High Impedance Fault Detector HMI โ€“ Human Machine Interface HST โ€“ Historian LGC โ€“ Scheme Logic MET โ€“ Substation Metering PDC โ€“ Phasor Data Concentrator PMU โ€“ Phasor Measurement Unit PQM โ€“ Power Quality Monitor RIO โ€“ Remote Input/Output Device RTU โ€“ Remote Terminal Unit/Data Concentrator SER โ€“ Sequence of Events Recorder 39
  • 42. 7.3 Suffixes and prefixes: A suffix letter or number may be used with the device number; for example, suffix N is used if the device is connected to a Neutral wire (example: 59N in a relay is used for protection against Neutral Displacement); and suffixes X, Y, Z are used for auxiliary devices. Similarly, the "G" suffix can denote a "ground"; hence a "51G" is a time overcurrent ground relay. The "G" suffix can also mean "generator", hence an "87G" is a Generator Differential Protective Relay while an "87T" is a Transformer Differential Protective Relay. "F" can denote "field" on a generator or "fuse", as in the protective fuse for a pickup transformer. Suffix numbers are used to distinguish multiple "same" devices in the same equipment such as 51-1, 51โ€“2. Device numbers may be combined if the device provides multiple functions, such as the instantaneous/time-delay AC over current relay denoted as 50/51. For device 16, the suffix letters further define the device: the first suffix letter is 'S' for serial or 'E' for Ethernet. The subsequent letters are: 'C' security processing function (e.g. VPN, encryption), 'F' firewall or message filter, 'M' network managed function, 'R' rotor, and โ€˜Sโ€™ switch and 'T' telephone component. Thus a managed Ethernet switch would be 16ESM. 40